8.4

CC-Link IE Field Network Function

8.4.1

Cyclic data update watch function

This function is used to watch the time interval between updates on cyclic data. When an update by cyclic transmission
remains to be done for a set period of time for watching, the module "continues its operation and produces external
outputs (HOLD)" or "stops its operation and external outputs (CLEAR)".
A halt in cyclic transmission is indicated by the status of the D LINK LED, flashing (data link established (cyclic
transmission stopped)) or off (data link not established (disconnected)).
Set either HOLD or CLEAR with the control output setting at CPU stop error.
For the control output setting at CPU stop error, refer to the following.
• HOLD/CLEAR function (Page 148, Section 8.3.2)
Master station
Remote device
station
(1) Setting method
1.
Set "Method selection" to "Param write (Station parameter)".
"CC IE Field Configuration" windowSelect the temperature control module from "List of
stations"[CC IE Field Configuration][Online][Parameter Processing of Slave Station]
2.
Set a time period for watching for "Cyclic data update watch time setting".
Cyclic data update watch time setting
When setting the cyclic data update watch time setting, set a time period longer than the link scan time.
224
Monitoring starts when cyclic data
are received for the first time.
Cyclic data
The cyclic data are updated within
the data link update time.
Item
When the cyclic data update interval
exceeds the set time, the control
becomes the HOLD/CLEAR status.
Cyclic data update
watch time setting
Setting range
• 0 (no watch)
• 1 to 20 (0.1 to 2 seconds, in steps of 100ms)
Common