9.13
CC-Link IE Field Network Synchronous Communication
Function
Using this function, the I/O module performs the I/O with a synchronization cycle of the master station that supports the

CC-Link IE Field Network synchronous communication function.

This enables the I/O module to operate at the same timing of other slave stations on the same network.
The operation of the extension I/O module is also synchronized.
This function can be used only when the master station that supports the CC-Link IE Field Network synchronous
communication function is used and "Mode switch" is set to "9: Automatical judgment mode".
(1) Applicable module and software
The CC-Link IE Field Network synchronous communication function cannot be used depending on the
combination of the I/O module and software package used. For details, refer to the following.
(a) When the master station is the simple motion module:
Module
NZ2GF2B1-16D
NZ2GF2B1-16T
NZ2GF2B1-16TE
NZ2GFCE3-16D
NZ2GFCE3-16DE
NZ2GFCM1-16D
NZ2GFCM1-16DE
NZ2GFCE3-16T
NZ2GFCE3-16TE
NZ2GFCM1-16T
NZ2GFCM1-16TE
NZ2GF2B1N-16D
NZ2GF2B1N-16T
NZ2GF2B1N-16TE
(b) When the master station is MELSEC iQ-R series module:
Module
NZ2GF2B1-16D
NZ2GF2B1-16T
NZ2GF2B1-16TE
NZ2GFCE3-16D
NZ2GFCE3-16DE
NZ2GFCM1-16D
NZ2GFCM1-16DE
NZ2GFCE3-16T
NZ2GFCE3-16TE
NZ2GFCM1-16T
NZ2GFCM1-16TE
NZ2GF2B1N-16D
NZ2GF2B1N-16T
NZ2GF2B1N-16TE
198
Serial number (first five digits)
"15102" or later
"16042" or later
"16111" or later
Serial number (first five digits)
"15102" or later
"16042" or later
"16111" or later
Serial number (first five digits) of
simple motion module
"15092" or later
Firmware version of the
RJ71GF11-T2/RJ71EN71
(no restriction)
Version of GX Works2
Version 1.501X or later
Version 1.513K or later
Version 1.501X or later
Version of GX Works3
Version 1.000A or later

Advertisement

Table of Contents
loading

Table of Contents