Appendix C
IO-Link Master Module and IO-Link Device Tag Definitions

IO-Link Master Module Tags

Table 28 - IO-Link Master Module Configuration Tags
Name
Counterxx.InputOffOnFilter
Counterxx.InputOnOffFilter
Counterxx.RolloverAtPreset
IOLinkxx.Disable
Ptxx.InputOffOnFilter
Ptxx.InputOnOffFilter
Ptxx.ChatterTime
98
This section describes the tags that are available for the ArmorBlock 5000 8-channel IO-Link
master module. The tables contained in this section list all tags that are available for the
module. Not all tags in the lists are used when the module is added to a project. Tag use varies
by module configuration.
The following types of tags are available:

Configuration Tags for IO-Link Master Module

Input Tags for IO-Link Master Module
Output Tags for IO-Link Master Module
Event Input Tags for IO-Link Master Module
Event Output Tags for IO-Link Master Module
Status Tags for IO-Link Master Module
Configuration Tags for IO-Link Master Module
Table 28
describes the available configuration tags ('C').
Data Type
Definition
The amount of time that a signal must be in the On state
SINT
before the input data indicates the On state.
The amount of time is indicated using an enumeration.
The amount of time that a signal must be in the Off state
SINT
before the input data indicates the Off state.
The amount of time is indicated using an enumeration.
BOOL
Set the counter to rollover to 0 at the preset value.
Set to disable the channel temporarily.
BOOL
When the channel is disabled, IO-Link communication on
the channel is deactivated.
The amount of time that a signal must be in the On state
SINT
before the input data indicates the On state.
The amount of time is indicated using an enumeration.
The amount of time that a signal must be in the Off state
SINT
before the input data indicates the Off state.
The amount of time is indicated using an enumeration.
The amount of time within which the number of input
INT
transitions are counted.
Rockwell Automation Publication 5032-UM001A-EN-P - April 2023
(as indicated by a 'C')
(as indicated by an 'I')
(as indicated by an 'O')
(as indicated by an 'EI')
(as indicated by an 'EO')
(as indicated by an 'S')
Valid Values
• 4 = 0 µs (default)
• 12 = 500 µs
• 13 = 1 ms
• 14 = 2 ms
• 15 = 5 ms
• 16 = 10 ms
• 17 = 20 ms
• 18 = 50 ms
• 4 = 0 µs (default)
• 12 = 500 µs
• 13 = 1 ms
• 14 = 2 ms
• 15 = 5 ms
• 16 = 10 ms
• 17 = 20 ms
• 18 = 50 ms
0 = Do not rollover (default)
1 = Rollover
0 = IO-Link communication is enabled (default)
1 = IO-Link communication is disabled
• 4 = 0 µs (default)
• 12 = 500 µs
• 13 = 1 ms
• 14 = 2 ms
• 15 = 5 ms
• 16 = 10 ms
• 17 = 20 ms
• 18 = 50 ms
• 4 = 0 µs (default)
• 12 = 500 µs
• 13 = 1 ms
• 14 = 2 ms
• 15 = 5 ms
• 16 = 10 ms
• 17 = 20 ms
• 18 = 50 ms
1...10000 ms