Table 23 - Special Connection Error Codes for IO-Link Device
Code
Description
This error is returned when a connection to an IO-Link device cannot be
16x033B
opened due to an IO-Link Data Storage Backup/Restore operation that is
in progress.
This error is returned when a connection to an IO-Link device cannot be
16x033C
opened because the device is not in the IO-Link Operate state.
This error is returned when an IO-Link device cannot enter its regular
16x033D
operating state due to a failed Data Storage Backup/Restore operation
in the IO-Link startup stage.
This error is returned when ADC is disabled and the selected connection
16x033F
type does not match the process data set currently used in the device.
This error is returned when there is an issue with the configuration of
16x001F
the device.
Module Fault Descriptions on Connection View
Figure 15
shows where a device fault description, which includes an error code that is
associated with the specific fault type, is indicated on the Connection view.
Table 23
describes the special connection error codes for IO-Link devices.
Figure 15 - Fault Description with Error Code on Connection View
Rockwell Automation Publication 5032-UM001A-EN-P - April 2023
Appendix B
Recommended Action
No action required. The connection is established after the Data Storage operation
is completed.
No action required if this is a temporary error.
If the error persists, check the IO-Link Status parameter in the XX Diagnostics - IO-
Link dialog. If the IO-Link Status parameter is not in the Operate state, check the
port-level IO-Link event log in the XX - IO-Link view.
For more information, see
IO-Link Event Log on page
This is usually caused by anomalous behavior of the IO-Link device.
Perform the steps as described in
General Troubleshooting Tips for Configuration
and Connection Issues on page
92.
If the error persists, contact technical support.
Complete one of the following:
1. If you want to use the selected connection type, go to the Configuration view,
perform Device Correlation Check, and select "Use Project Values".
2. If you want to use the process data set that is currently used in the device, go
offline with your project, go to the device Module Definition, and change the
connection type to match the device.
Perform the steps as described in
General Troubleshooting Tips for Configuration
and Connection Issues on page
92.
If the error persists, contact technical support.
Troubleshoot Your IO-Link Device
95.
91