Use the Studio 5000 Logix
Designer Application for
Troubleshooting

Troubleshoot Your IO-Link Device

This appendix describes how to identify and troubleshoot issues with your IO-Link devices.
The Studio 5000 Logix Designer application indicates the presence of fault conditions.
Fault conditions are reported in the following ways:

Warning Signal in the I/O Configuration Tree

Status and Fault Information in Module Properties
Studio 5000 Logix Designer Application Tag Editor
Warning Signal in the I/O Configuration Tree
As shown in
Figure
13, a warning icon appears in the I/O Configuration tree when a fault
occurs.
Figure 13 - Warning Signal in I/O Configuration Tree
If a warning signal appears in the I/O Configuration tree, make sure that:
The device is powered up and properly wired to the module.
There is no fault status on the channel.
In the XX Diagnostics - IO-Link dialog, check if the IO-Link Status parameter is in the
Operate state. If the parameter is not in the Operate state, check the XX - IO-Link Port
Event Log dialog for more information.
You can access the XX Diagnostics - IO-Link and XX - IO-Link Port Event Log dialogs
from the IO-Link master Module Properties > XX - IO-Link view. For more information,
see
XX - IO-Link on page
Rockwell Automation Publication 5032-UM001A-EN-P - April 2023
50.