Chapter 6
Configure the IO-Link Device
66
3. Enter a Name for the device.
If you want to configure the other settings during this step, see
Properties on page 67
4. Select OK to save the configuration.
If you are in online mode, a prompt appears to request to inhibit the device. We
recommend inhibiting the device if the device is not fully configured or not ready to be
put into operation currently.
5. Repeat steps 2...4 to add another device, or close the Select Module Type dialog. If you
selected the Close on Create checkbox in step 2, you must start from step 1 to add
another module.

Add a Preconfigured Device

You can add a preconfigured IO-Link device to your system and use this device configuration
across other devices in the system.
We recommend attaching your preconfigured IO-Link device to a new IO-Link master module,
or a used IO-Link master module that is restored to the factory default state, to help ensure
that the previous device configuration in the IO-Link master module does not overwrite the
configuration in the device. Restoring the module to the factory default state clears all device
configuration that is stored on all ports from the module.
If you use an IO-Link master module that is new or has been reset to the factory default state,
follow these steps add your preconfigured device.
1. Go online with your project.
2. Attach your preconfigured IO-Link device to an IO-Link or Fallback channel.
3. Follow the steps as described in
4. In the device Module Properties > Configuration view, perform Device Correlation
Check, select "Use Device Values", and select Apply.
Rockwell Automation Publication 5032-UM001A-EN-P - April 2023
for more information.
Discover Modules
to add the device.
Edit the IO-Link Device