Table 24 - Fault and Status Information
Parameter
Description
Major Fault
Indicates whether a major fault is present on the device.
Minor Fault
Indicates whether a minor fault is present on the device.
Indicates whether the Data Storage copy in the IO-Link master
Data Storage Match
module is synchronized with the IO-Link device.
Fault and Status Information on Device Info View
Figure 16
shows where the major and minor fault information, and the Data Storage Match
status are indicated on the Device Info view.
Table 24
describes the fault and status information for the IO-Link device.
Figure 16 - Major and Minor Fault Information and Data Storage Match Status
Rockwell Automation Publication 5032-UM001A-EN-P - April 2023
Appendix B
Recommended Action
Complete the following:
• Check the device-level IO-Link event log.
• Check the device status in the Parameters view.
• Follow the instructions in the documentation for your device to troubleshoot
the fault.
If the device is attached to an IO-Link (non-Fallback) channel and the device
connection is running but the Data Storage Match parameter shows that it is
not matched, contact your device manufacturer.
If the device is on a Fallback channel, complete the following steps:
• Uninhibit the device and verify that the connection is running.
• Inhibit the device and apply the change.
• Go to the Device Info view and refresh the view until the Data Storage Match
parameter shows that it is matched.
• If the Data Storage Match parameter does not show that it is matched after
some time, contact your device manufacturer.
NOTE: After you uninhibit the device, you cannot see the actual status of the
Data Storage Match parameter in the Device Info view.
Troubleshoot Your IO-Link Device
93