6. In the IO-Link device Module Properties > Device Info view, select Reset Module to
Factory Default.
7. In the IO-Link device Module Properties > Connection view, clear the Inhibit Module
checkbox and select Apply.
Data Storage Backup/Restore is enabled on the port when connection is established
and the device configuration that is stored in the IO-Link master module is downloaded
to the replacement device.

Replace a Device on a Fallback Channel

WARNING: Before you replace a device that is assigned to a Fallback channel,
you must first inhibit the device.
To replace a device on a Fallback channel, complete these steps.
1. Go online with your project.
2. In the IO-Link device Module Properties > Connection view, select the Inhibit Module
checkbox and select Apply.
3. Follow the steps that are described in the other scenarios that apply to your device.
4. After you have completed those steps, in the IO-Link device Module Properties >
Connection view, select the Inhibit Module checkbox and select Apply.
Replace with a Used Master Module when any Device Supports DS and
ADC Disabled
To replace an IO-Link master module in this scenario, complete these steps.
1. In the IO-Link master Module Properties > Connection view, select the Inhibit Module
checkbox and select Apply.
2. Replace the IO-Link master module.
3. If using a previously configured IO-Link master module, reset the module to the factory
default state. For instructions. see
IMPORTANT You must reset the IO-Link master module to factory default
4. In the IO-Link master Module Properties > Connection view, clear the Inhibit Module
checkbox and select Apply.
The device configurations are backed up to the replacement IO-Link master module
when device connections are established.

Replace a Master Module and Devices with Device ADC Disabled

Verify that you have completed the procedure as described in
To replace an IO-Link master module and all IO-Link devices in this scenario, complete these
steps.
1. In the IO-Link master Module Properties > Connection view, select the Inhibit Module
checkbox and select Apply.
2. Replace the IO-Link master module and IO-Link devices.
3. In the IO-Link device Module Properties > Configuration view, perform Device
Correlation Check and select "Use Project Values".
Repeat this step for all IO-Link devices with ADC disabled.
4. In the IO-Link master Module Properties > Connection view, clear the Inhibit Module
checkbox and select Apply.