Table 28 - IO-Link Master Module Configuration Tags (Continued)
Name
Ptxx.ChatterCount
Ptxx.CaptureOffOnEn
Ptxx.CaptureOnOffEn
Ptxx.TimestampLatchEn
Ptxx.FaultMode
Ptxx.FaultValue
Ptxx.ProgMode
Ptxx.ProgValue
Ptxx.FaultFinalState
Ptxx.FaultValueStateDuration
Ptxx.ProgramToFaultEn
Ptxx.NoLoadEn
Ptxx.DiConfig.InputOffOnFilter
Ptxx.DiConfig.InputOnOffFilter
Ptxx.DiConfig.ChatterTime
Data Type
Definition
The number of input transitions that are considered
chatter.
Chatter can cause the module to time stamp invalid
SINT
input transitions. Typically, chattering signals cause
inputs to transition falsely many times in a relatively
short period.
Set to capture a time stamp when the input transitions
BOOL
from Off to On.
Set to capture a time stamp when the input transitions
BOOL
from On to Off.
Set to latch time stamps.
BOOL
When a time stamp is latched, it is not overwritten
until acknowledged.
Determines the action that the output takes when a
connection fault occurs.
At fault occurrence, the output holds its last state or
BOOL
transitions to the value set in FaultValue.
The channel continues this action for the length of time
set in FaultValueStateDuration.
Defines the state that the output assumes if a
BOOL
communication fault occurs when FaultMode = 0.
Determines the action that the output takes when the
controller transitions to Program mode or the
BOOL
connection to the module is inhibited.
At the transition to Program mode, the output holds its
last state or transitions to the value set in ProgValue.
Defines the state that the output assumes when
BOOL
the connection transitions to Program mode when
ProgMode = 0.
If FaultValueStateDuration is nonzero, set the final
BOOL
output state after the configured
FalueValueStateDuration timeout occurs.
Set the length of time that the FaultMode state is held
SINT
before the FinalFaultState being applied.
Determines if the output transitions to Fault mode when
BOOL
the connection faults while in Program mode.
Set to enable No Load detection. When enabled, if a wire
is disconnected from an output that is turned Off (No
Load condition), the I.Ptxx.NoLoad tag changes to 1.
BOOL
This tag is not available when the channel mode is set to
"Digital Output, Short Circuit" or "Digital Output, Group
Short Circuit".
The amount of time that a signal must be in the On state
SINT
before the input data indicates the On state.
The amount of time is indicated using an enumeration.
The amount of time that a signal must be in the Off state
SINT
before the input data indicates the Off state.
The amount of time is indicated using an enumeration.
The amount of time within which the number of input
INT
transitions are counted.
Rockwell Automation Publication 5032-UM001A-EN-P - April 2023
Appendix C
IO-Link Master Module and IO-Link Device Tag Definitions
Valid Values
0 = Disabled (default)
2...127 = Enabled
0 = Do not capture (default)
1 = Capture
0 = Do not capture (default)
1 = Capture
0 = Do not latch (default)
1 = Latch
0 = Transition to user-defined value (default)
1 = Hold last state
0 = Output is off (default)
1 = Output is on
0 = Transition to user-defined value (default)
1 = Hold last state
0 = Output is off (default)
1 = Output is on
0 = Output is off (default)
1 = Output is on
• 0 = Forever (default)
• 1 = 1 s
• 2 = 2 s
• 5 = 5 s
• 10 = 10 s
0 = Remain in Program mode (default)
1 = Transition to Fault mode
0 = No Load detection disabled
1 = No Load detection enabled
• 4 = 0 µs (default)
• 12 = 500 µs
• 13 = 1 ms
• 14 = 2 ms
• 15 = 5 ms
• 16 = 10 ms
• 17 = 20 ms
• 18 = 50 ms
• 4 = 0 µs (default)
• 12 = 500 µs
• 13 = 1 ms
• 14 = 2 ms
• 15 = 5 ms
• 16 = 10 ms
• 17 = 20 ms
• 18 = 50 ms
1...10000 ms