Edit the IO-Link Device
Properties
If you use an IO-Link master module that is used, follow these steps add your preconfigured
device.
1. Go online with your project.
2. In the IO-Link master Module Properties, complete these steps to disable Data Storage
on the IO-Link port.
a. In the IO-Link channel view, select the Disable Channel checkbox.
b. In the Connection view, clear the Inhibit Module checkbox.
c. Select Apply.
3. Attach your preconfigured device to the IO-Link port that was disabled in step 2.
4. In the IO-Link master Module Properties > IO-Link channel view, clear the Disable
Channel checkbox and select Apply.
5. Follow the steps as described in
Before you select OK, select Inhibit Module in the IO-Link device Module Properties >
Connection view.
6. In the IO-Link device Module Properties > Configuration view, perform Device
Correlation Check, select "Use Device Values", and select Apply. The preconfigured
device configuration is backed up to the project.
7. In the IO-Link device Module Properties > Connection view, clear the Inhibit Module
checkbox and select Apply. Data Storage is enabled on the IO-Link port.
8. When the connection is running, perform Device Correlation Check. If there are
differences, it means that the Data Storage copy in the IO-Link master module has
overwritten the configuration in the device. Inhibit the device, perform Device
Correlation Check again, select "Use Project Values", and select Apply to restore the
preconfigured device configuration to the device. After successfully restoring the
device configuration, the preconfigured device configuration is automatically backed
up to the IO-Link master module.
After you have added the IO-Link device to your project, you can use the different views in the
device Module Properties window to change the device properties.
The following views for the IO-Link device are described in this section.
General View
Connection View
Device Info View
Configuration View
Parameters View
Rockwell Automation Publication 5032-UM001A-EN-P - April 2023
Chapter 6
Discover Modules
to add the device.
Configure the IO-Link Device
67