Protected Operations

Table 2 - Protected Operations on ArmorBlock 5000 8-channel IO-Link Master Modules and IO-Link Devices
Current
Firmware Update
Operation
(1)
Request
Connection
not running
Connection
running
Firmware update
in process
(1) Firmware update for IO-Link devices is not supported.
(2) Configuration change is accepted in the following scenarios:
- Changes are made in the Module Properties window and you select Apply.
- Changes are made in the Configuration tags and you send a Reconfigure Module MSG instruction to the module or device.
- IO-Link device configuration changes are made in the ladder diagram through connected explicit messaging.
(3) The difference between Rejected and Not allowed is that rejected activities can be attempted in the Studio 5000 Logix Designer application but do not take effect. The activities that are not
allowed, that is, attempts to change the Connection or Data Format used, do not occur in the Studio 5000 Logix Designer application.
For example, if you attempt to reset a module that is connected to the controller, the Studio 5000 Logix Designer application executes the request and alerts you that it was rejected. If you
attempt to change the data format on a module that is connected to a controller, the Studio 5000 Logix Designer application does not execute the attempted change. The application only
alerts you that the change is not allowed. In this case, if the change is attempted online, the Module Definition dialog field that changes the data format is disabled.
(4) The change occurs after the connection is closed and reopened. You can close and reopen the connection in the following ways:
- Change the project while it is online and select Apply or OK in the Module Properties window. In this case, before the change is made, a dialog box alerts you of the ramifications before the
change is made.
- Change the project while it is offline and download the updated project before going online again.
To maintain the secure operation of your IO-Link master module and IO-Link devices,
operations that can disrupt the module and device operations are restricted based on the
operating mode.
Table 2
describes the restrictions.
Connection
Reset Request
Request
Rejected
Rejected
For more information on the protected operating modes, see the following:
Protected Mode for IO-Link Master Module on page
Protected Mode for IO-Link Devices on page
Rockwell Automation Publication 5032-UM001A-EN-P - April 2023
Activity
Connection or
Configuration
Data Format
Change
Change
Accepted
(2)
(3)
Accepted
Not allowed
Rejected
36.
Chapter 1
Introduction
Electronic Keying
RPI Change
Change
(4)
Accepted
21.
15

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents