Software Configurable

Configurable Channel
Modes

Fault and Status Reporting

Module Features

This chapter describes the general features of the ArmorBlock 5000 8-channel IO-Link master
module.
To learn more about the other features of the IO-Link master module, see the following:
I/O Channel Features on page
Common Features of IO-Link Device Integration on page
You use the Studio 5000 Logix Designer application to configure the module, monitor system
operation, and troubleshoot issues.
The software makes module configuration easier and more reliable by minimizing the need for
tasks such as setting hardware switches and jumpers.
You can configure each channel of the ArmorBlock 5000 8-channel IO-Link master module as
IO-Link, digital input, or digital output mode. You can also configure some channels as a
Class B power supply for IO-Link devices.
To configure the channel mode, see
The ArmorBlock 5000 8-channel IO-Link master module reports fault and status data along
with channel data. Fault and status data is reported in the following ways:
Fault and status bits in the input data tags
Studio 5000 Logix Designer application
Module status indicators
Table 3
lists the fault and status tags that are available for the IO-Link master module in the
Studio 5000 Logix Designer application.
Table 3 - Fault and Status Tags for ArmorBlock 5000 8-channel IO-Link Master Module
Data Type
Tag Name
Fault
ConnectionFaulted
RunMode
DiagnosticActive
Status
DiagnosticSequenceCount
(1) This tag provides module-wide data and affects all channels simultaneously.
For more information on fault reporting in the Studio 5000 Logix Designer application and
module status indicators, see
Rockwell Automation Publication 5032-UM001A-EN-P - April 2023
23.
General View on page
45.
Triggering Event That Sets the Tag
(1)
The controller loses its connection to the module.
The module is in Run Mode.
Indicates if any diagnostics are active or if the prognostics
threshold is reached.
The count increments each time a diagnostic condition is detected
or removed.
You can monitor this count during module operation and check the
channel diagnostics when the count value changes.
Troubleshoot Your IO-Link Master Module on page
2
Chapter
29.
79.
17