Fault and Status Reporting

The module sends fault and status data with channel data to the controller. The data is
returned through module tags that you can monitor in your Studio 5000 Logix Designer
application.
The ArmorBlock 5000 8-channel IO-Link master module provides the fault and data status in a
channel-centric format.
Table 5
lists the fault and status tags that are available for the IO-Link master module
channels in the Studio 5000 Logix Designer application.
Table 5 - Fault and Status Tags for ArmorBlock 5000 8-channel IO-Link Master Module Channels
Data Type
Tag Name
Ptxx.Fault
Fault
Counterxx.Fault
IOLinkxx.Fault
Ptxx.Data
Status
Counterxx.Data
IOLinkxx.Uncertain
We recommend that you monitor the tags in your program to make sure that the application is
operating as expected.
IMPORTANT Once the condition that causes the Fault or Uncertain tag to change to 1
is removed, the tag automatically resets to 0. The Studio 5000 Logix
Designer application controls the tags. You cannot change the status of
the tags.
Remember that in some system configurations, the tag is not reset
immediately after the condition is removed. The tag typically resets after
a short delay.
Table 6
lists the conditions that are shown in the channel diagnostics and diagnostic
assemblies.
Table 6 - Diagnostic Conditions
Diagnostic Condition
SAPowerFault
SAPowerFaultTimestamp
LAPowerFault
LAPowerFaultTimestamp
SAPowerShortCircuit
SAPowerShortCircuitTimestamp
LAPowerShortCircuit
LAPowerShortCircuitTimestamp
NoLoad
NoLoadTimestamp
ShortCircuit
ShortCircuitTimestamp
For more information on fault reporting, see
page
79.
Rockwell Automation Publication 5032-UM001A-EN-P - April 2023
Chapter 3
Triggering Event That Sets the Tag
The channel data quality is bad.
The counter data quality is bad.
The IO-Link data quality is bad.
The point input status is 0 or 1.
The counter input status is 0 or 1.
LA power for Class B device is faulted.
Description
Indicates whether a fault exists on SA power
The most recent time a fault on SA power occurred
Indicates whether a fault exists on LA power
The most recent time a fault on LA power occurred
Indicates whether a short circuit or overcurrent condition exists
on SA power
The most recent time a short circuit or overcurrent condition on
SA power occurred
Indicates whether a short circuit or overcurrent condition exists
on LA power
The most recent time a short circuit or overcurrent condition on
LA power occurred
Indicates whether a No Load condition exists
The most recent time a No Load condition occurred
Indicates whether a short circuit condition exists
The most recent time a No Load condition occurred
Troubleshoot Your IO-Link Master Module on
I/O Channel Features
27