Table 34 - IO-Link Device Configuration Tags
Name
ProgramToFaultEn
FaultMode
ProgMode
Device Configuration Parameter Name
Table 35 - IO-Link Device Input Tags
Name
RunMode
ConnectionFaulted
DiagnosticActive
CIPSyncValid
CIPSyncTimeout
DiagnosticSequenceCount

Configuration Tags for IO-Link Device

Table 34
describes the available configuration tags ('I').
Data Type
Definition
Determines if the output process data behavior follows
BOOL
the FaultMode or ProgMode setting when a connection
fault occurs in Program mode.
Determines the behavior the IO-Link channel takes with
SINT
output process data if a communication fault occurs.
Determines the behavior the IO-Link channel takes with
SINT
output process data if the connection transitions to
Program mode.
Device configuration parameters.

Input Tags for IO-Link Device

Table 35
describes the available input tags ('I').
Data Type
Definition
BOOL
Indicates the operating state of the input.
Indicates if a connection is running.
BOOL
The device sets this tag to 0 when connected. If the
device is not connected, it sets this tag to 1.
Indicates if any diagnostics are active or if the
BOOL
prognostics threshold is reached.
Indicates if the device is synchronized with a 1588
BOOL
master.
Indicates if the device was previously synchronized with
BOOL
a 1588 master but is now timed out.
Increments for each time a distinct diagnostic condition
is detected, and when a distinct diagnostic condition
SINT
transitions from detected to not detected.
Sets to zero by product reset or power cycle. Wraps
from 255 (-1) to 1 skipping zero.
Rockwell Automation Publication 5032-UM001A-EN-P - April 2023
Appendix C
IO-Link Master Module and IO-Link Device Tag Definitions
Valid Values
0 = Follows the ProgMode setting
1 = Follows the FaultMode setting
• 0 = Device Decides
Output process data is disabled when the connection
is faulted.
• 1 = Hold Last Process Data Output
Output process data remains enabled and the IO-Link
master module holds the last output process data
received when the connection is faulted.
• 2 = All Zeros
Output process data remains enabled and the IO-Link
master module sends all zeros as output process data
when the connection is faulted.
• 0 = Device Decides
Output process data is disabled when the connection
transitions to Program mode.
• 1 = Hold Last Process Data Output
Output process data remains enabled and the IO-Link
master module holds the last output process data
received when the connection transitions to Program
mode.
• 2 = All Zeros
Output process data remains enabled and the IO-Link
master module sends all zeros as output process data
when the connection transitions to Program mode.
Device-specific
Valid Values
0 = Idle
1 = Run mode
0 = Connection running
1 = Connection not running
0 = No diagnostics active
1 = One or more diagnostics are active or the prognostics
threshold is reached
0 = Device not synchronized
1 = Device synchronized
0 = A valid time master has not timed out
1 = A valid time master has timed out
-128...+127
The value of 0 is skipped except during device power-
up.