Install The Mounting Base; Install The I/O Module; Added Grounding Information - Rockwell Automation Allen-Bradley C Series Installation Instructions Manual

Point i/o 2 current and 2 voltage input analog modules
Hide thumbs Also See for Allen-Bradley C Series:
Table of Contents

Advertisement

POINT I/O 2 Current and 2 Voltage Input Analog Modules Installation Instructions

Install the Mounting Base

To install the mounting base on the DIN rail (Allen-Bradley® part number 199-DR1; 46277-3; EN50022), proceed as follows:
ATTENTION: This product is grounded through the DIN rail to chassis ground. Use zinc-plated chromate-passivated steel DIN rail to assure proper
grounding. The use of other DIN rail materials (for example, aluminum or plastic) that can corrode, oxidize, or are poor conductors, can result in improper or
intermittent grounding. Secure DIN rail to mounting surface approximately every 200 mm (7.8 in.) and use end-anchors appropriately. Be sure to ground the
DIN rail properly. See Industrial Automation Wiring and Grounding Guidelines, Rockwell Automation publication 1770-4.1, for more information.
WARNING: When used in a Class I, Division 2, hazardous location, this equipment must be mounted in a suitable enclosure with proper wiring method that
complies with the governing electrical codes.
1.
Position the mounting base vertically above the installed units (adapter, power supply, or existing module).
2.
Slide the mounting base down allowing the interlocking side pieces to engage the adjacent module or adapter.
3.
Press firmly to seat the mounting base on the DIN rail. The mounting base snaps into place.
Be sure that the orange DIN rail locking screw is in the horizontal position and that it has engaged the DIN rail.
4.
ATTENTION: Use the end cap from your adapter or interface module to cover the exposed interconnections on the last mounting base on the DIN rail. Failure
to do so could result in equipment damage or injury from electric shock.

Install the I/O Module

The module can be installed before or after base installation. Make sure that the mounting base is correctly keyed before installing the module into the mounting base. In addition,
make sure that the mounting base locking screw is positioned horizontal referenced to the base.
WARNING: When you insert or remove the module while backplane power is on, an electric arc can occur. This could cause an explosion in hazardous location
installations. Be sure that power is removed or the area is nonhazardous before proceeding. Repeated electrical arcing causes excessive wear to contacts on
both the module and its mating connector. Worn contacts may create electrical resistance that can affect module operation.
POINT I/O Terminal Bases
1734-TB Base
6
1734-TOP Base
Turn the keyswitch to align the number with
the notch. Notch position 3 is shown.
Make sure that the DIN rail locking
screw is in the horizontal position.
Rockwell Automation Publication 1734-IN027E-EN-E - June 2023
Make sure that the DIN rail locking screw is in
the horizontal position.
Turn the keyswitch to align the number with the
notch. Notch position 1 is shown.