From the Controller Organizer pane, expand Tasks > Main Task > MainProgram.
1. Create message type user tags for each request.
2. Create associated response user tags for each new user-defined diagnostic assembly
type.
3. Add the user tags to your ladder program.
4. Expand the message tag to open the message configuration dialog.
5. On the Configuration tab, enter the following information:
- Service Type = Get Attribute Single
- Class = 4
- Instance =
• 32775 (0x8007) Diagnostic IO-Link Master 2 Port Ethernet Assembly
• 32776 (0x8008) Diagnostic IO-Link Master Assembly A
• 32777 (0x8009) Diagnostic IO-Link Master Assembly B
• 32778 (0x800A) Diagnostic IO-Link Master Assembly C
• 32779 (0x800B) Diagnostic IO-Link Master Assembly D
• 771 (0x303) Diagnostic Counters Ethernet Adapter Assembly
- Attribute = 3
- Destination Element = User-defined type suitable for the instance entered
6. On the Communication tab, select the path to the module that you wish to send the
message to.
7. Select OK.
8. Download the project and set to Run mode.
You can monitor the user-defined tag values from the Program Parameters and Local Tags
window, under the MainProgram task in the Controller Organizer pane.