Rockwell Automation POINTBlock Series User Manual

Rockwell Automation POINTBlock Series User Manual

I/o digital and analog modules
Table of Contents

Advertisement

POINT I/O Digital and Analog Modules and
POINTBlock I/O Modules
User Manual
(Catalog Numbers 1734-IA2, 1734-IM4, 1734-IB2, 1734-IB4, 1734-IB8, 1734-IB4D, 1734-IM2,
1734-IM4, 1734-IV2, 1734-IV4,
1734-IV8, 1734-OA2, 1734-OA4, 1734-OB2, 1734-OB2EP,
1734-OB2E, 1734-OB4, 1734-OB4E, 1734-OB8, 1734-OB8E,
1734-OV2E, 1734-OV4E, 1734-OV8E, 1734-OW2, 1734-OW4,
1734-OX2, 1734-IE2C, 1734-IE2V, 1734-OE2C, 1734-OE2V,
1734D-IA16, 1734D-IA8XOA8, 1734D-IA8XOW8, 1734D-IB16,
1734D-IB8XOB8, 1734D-IB8XOW8)

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the POINTBlock Series and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Rockwell Automation POINTBlock Series

  • Page 1 POINT I/O Digital and Analog Modules and POINTBlock I/O Modules User Manual (Catalog Numbers 1734-IA2, 1734-IM4, 1734-IB2, 1734-IB4, 1734-IB8, 1734-IB4D, 1734-IM2, 1734-IM4, 1734-IV2, 1734-IV4, 1734-IV8, 1734-OA2, 1734-OA4, 1734-OB2, 1734-OB2EP, 1734-OB2E, 1734-OB4, 1734-OB4E, 1734-OB8, 1734-OB8E, 1734-OV2E, 1734-OV4E, 1734-OV8E, 1734-OW2, 1734-OW4, 1734-OX2, 1734-IE2C, 1734-IE2V, 1734-OE2C, 1734-OE2V, 1734D-IA16, 1734D-IA8XOA8, 1734D-IA8XOW8, 1734D-IB16, 1734D-IB8XOB8, 1734D-IB8XOW8)
  • Page 2 In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment.
  • Page 3 Summary of Changes This publication contains new and revised information not in the last release. New Information See the table that shows what we added to this publication. Item Added Cat. No. Input Modules 1734-IA4 1734-IB4D 1734-IM4 Output Modules 1734-OA4 Specialty Modules 1734-IR2E One-piece Terminal Bases...
  • Page 4 Summary of Changes Notes: Publication 1734-UM001D-EN-P - April 2008...
  • Page 5: Table Of Contents

    Table of Contents Purpose of This Manual........13 Preface Who Should Use This Manual.
  • Page 6 Table of Contents 1734-IA2 and 1734-IA4 120 V ac Input Modules ... . 53 1734-IM2 and 1734-IM4 220V ac Input Modules ... . . 55 1734-IM2 120V ac 2 Input Module Wiring Diagram.
  • Page 7 Table of Contents Chapter 3 About This Chapter ........77 Install POINTBlock I/O Modules Wiring POINTBlock Modules .
  • Page 8 Table of Contents Chapter 4 About This Chapter ........97 POINT I/O Module Data Digital Input Modules .
  • Page 9 Table of Contents Chapter 5 About This Chapter ........121 Calibrate Your Analog Modules Tools Required to Calibrate Your Analog Modules .
  • Page 10 Table of Contents Appendix A About This Appendix ........165 Default Data Maps Digital Module Default Data Maps .
  • Page 11 Table of Contents Appendix C About This Appendix ........183 Configure POINT I/O Modules in Use the Help Button .
  • Page 12 Table of Contents Notes Publication 1734-UM001D-EN-P - April 2008...
  • Page 13: Preface

    Preface This manual describes how to install, configure, and troubleshoot your Purpose of This Manual POINT I/O modules. The POINT I/O modules in this manual are DeviceNet ready. Each module can exist on the DeviceNet network as one of the following: •...
  • Page 14: Additional Resources

    Preface Refer to this table for a list of related 1734 products and documentation. Most Additional Resources of these are available from http://literature.rockwellautomation.com/. For specification and safety certification information, refer to the installation instructions. Resource Description Analog Modules Analog Current and Voltage Input Module Installation Instructions, Provides installation information for 1734-IE2C and 1734-IE2V publication 1734-IN027 modules...
  • Page 15 Preface Resource Description Protected Source Output Module Installation Instructions, Provides installation information about 1734-OB2E, 1734-OB4E, and publication 1734-IN056 1734-OB8E modules Protected Source Output Module Installation Instructions, Provides installation information about 1734-OB2, 1734-OB4, and publication 1734-IN018 1734-OB8 modules POINTBlock Modules 8 ac Input/8 ac Output Module Installation Instructions, Provides installation information about 1734D-IA8XOA8 modules publication 1734-IN022 8 ac Input/8 ac Relay Output Module Installation Instructions,...
  • Page 16 Preface Resource Description Encoder/Counter Module User Manual, publication 1734-UM006 Describes how to use 1734-IJ and 1734-IK modules Very High-speed Counter Module Installation Instructions, Provides installation information about 1734-VHSC5 and publication 1734-IN003 1734-VHSC24 modules Very High-speed Counter Module User Manual, Describes how to use 1734-VHSC5 and 1734-VHSC24 modules publication 1734-UM003 Address Reserve Module Installation Instructions, Provides installation information about 1734-ARM modules...
  • Page 17: About The Modules

    Chapter About the Modules This chapter introduces POINT I/O and related modules to include the About This Chapter following: • Digital modules • Relay output modules • Analog modules • Specialty modules • Power supplies, wiring base assemblies, and miscellaneous module This table lists 1734 digital modules.
  • Page 18: Input Modules

    About the Modules This table lists the 1734D POINTBlock modules. POINTBlock Module Description Cat. No. 8 ac input and 8 ac output 1734D-IA8XOA8 and 1734-IA8XOA8S 8 ac input and 8 relay output 1734D-IA8XOW8 and 1734-IA8XOW8S 8 dc input and 8 dc output 1734D-IB8XOB8 and 1734-IB8XOB8S 8 dc input and 8 relay output 1734D-IB8XOW8 and 1734-IB8XOW8S...
  • Page 19: Relay Output Modules

    About the Modules • Autobaud (will match baud of existing devices on the network) • Sequential auto addressing The 1734-OV2E, 1734-OV4E, and 1734-OV8E modules are protected sink output modules protected to 1 A. The outputs are not isolated from each other.
  • Page 20: Analog Modules

    About the Modules The 1734 analog modules consist of input modules (1734-IE2C and Analog Modules 1734-IE2V) and output modules (1734-OE2C and 1734-OE2V). Each module has two single-ended, non-isolated channels. Cat. No. Module Type Number Resolution Channels 1734-IE2C Analog Input 16 bits across 0…21 mA 1734-IE2V Analog Input 15 bits plus sign across -10…10V...
  • Page 21: Input Modules

    About the Modules Input Modules These features are available on input modules. • Latching alarms, when set, latch low- and high-alarm status information. Available alarms include: – Low. – Low Low. – High. – High High. • Disable alarms - disables all channel alarms and faults so they are not reported in the channel status field.
  • Page 22: Specialty Modules

    About the Modules For more information about the following 1734 specialty modules, refer to the Specialty Modules installation instructions and user manuals listed in the Related Products and Documentation section of this manual. Module Description Cat. No. 5V Encoder/Counter Module 1734-IJ 24V Encoder/Counter Module 1734-IK...
  • Page 23: Install Point I/O Modules

    Chapter Install POINT I/O Modules Read this chapter for installation and wiring information including how to About This Chapter complete the following: • Install the mounting base assembly. • Install an I/O module. • Install the removable terminal block. • Remove a mounting base. •...
  • Page 24: Install The Mounting Base Assembly

    Install POINT I/O Modules POINT I/O is grounded through the DIN rail to chassis ground. ATTENTION Use zinc-plated, yellow-chromated steel DIN rail to assure proper grounding. The use of DIN rail materials (for example, aluminum or plastic) that can corrode, oxidize, or are poor conductors, can result in improper or intermittent grounding.
  • Page 25 Install POINT I/O Modules To install the mounting base assembly on the DIN rail, proceed as follows. Slide-in Writable Label Module Locking Mechanism Insertable I/O Module Module Wiring Diagram DIN Rail Locking Screw (orange) RTB Removing Handle Mechanical Keying (orange) Removable Terminal Block (RTB) Interlocking Side Pieces...
  • Page 26: Install An I/O Module

    Install POINT I/O Modules 2. Slide the mounting base down, allowing the interlocking side pieces to engage the adjacent module, power supply, or adapter. 31586 3. Press firmly to seat the mounting base on the DIN rail. The mounting base snaps into place. 4.
  • Page 27 Install POINT I/O Modules 1. Using a bladed screwdriver, rotate the keyswitch on the mounting base clockwise until the number required for the type of module aligns with the notch in the base. Notch Position 3 is shown. Module Keyswitch Position 1734-ARM 1734-CTM, 1734-VTM 1734-IA2, 1734-IA4...
  • Page 28: Install The Removable Terminal Block

    Install POINT I/O Modules 3. Insert the module straight down into the mounting base and press to secure, locking the module into place. 308802 A removable terminal block is supplied with your mounting base assembly. To Install the Removable remove, pull up on the removable terminal block (RTB) handle. This lets you Terminal Block remove and replace the base as necessary without removing any of the wiring.
  • Page 29: Remove A Mounting Base

    Install POINT I/O Modules To remove a mounting base, you must remove any installed module, and Remove a Mounting Base remove the removable terminal block (RTB), if wired. When you insert or remove the module while backplane power WARNING is on, an electrical arc can occur. This could cause an explosion in hazardous location installations.
  • Page 30: Wiring Digital Modules

    Install POINT I/O Modules Refer to this section to wire digital modules. Wiring Digital Modules 1734-IB2, 1734-IB4, and 1734-IB8 Sink Input Modules 1734-IB4 1734-IB8 1734-IB2 Module Module Module Status Status Status Network Network Network Status Status Status NODE: NODE: NODE: 24VDC 24VDC 24VDC...
  • Page 31 Install POINT I/O Modules 1734-IB4 Module Wiring Diagram Sink Input In 0 In 1 2-wire 3-wire In 2 In 3 Prox Prox Prox Prox 41967 V = 12/24V dc C = Common Channel Input Common Voltage Connect common on 3- proximity switches. 12/24V dc is supplied through the internal power bus. 1734-IB8 Module Wiring Diagram Sink Input 3-wire...
  • Page 32 Install POINT I/O Modules When connecting more than one wire in a termination point, ATTENTION make sure that both wires are the same gauge and type. Example of Wiring - 1734-IB8 Module Using 2-Wire Proximity Switches Module Module Status Status Network Network Status...
  • Page 33 Install POINT I/O Modules Example of Wiring - 1734-IB8 Module Using 3-wire Proximity Switches 1734-IB8 1734-VTM 1734-CTM 2-wire Prox In 0 In 1 In 2 In 3 In 4 In 5 3-wire Prox In 7 In 6 43927 V = Voltage Out C = Common Example of Wiring - 1734-IB8 Module Using 3-wire Proximity Switches Module...
  • Page 34: 1734-Ib4D Modules

    Install POINT I/O Modules 1734-IB4D Modules Module Status Network Status Status of Input 0 Status of Input 1 Status of Input 2 Note that voltage and current are Status of Input 3 daisychained from either the adapter, 1734-FPD module, or 1734-EP24DC module.
  • Page 35: 1734-Iv2, 1734-Iv4, And 1734-Iv8 Source Input Modules

    Install POINT I/O Modules 1734-IV2, 1734-IV4, and 1734-IV8 Source Input Modules 1734-IV2 1734-IV4 1734-IV8 Module Status Module Status Module Status Module Module Module Status Status Status Network Network Network Status Network Status Network Network Status Status Status Status NODE: NODE: NODE: 24VDC 24VDC...
  • Page 36 Install POINT I/O Modules 1734-IV4 Module Wiring Diagram Source Input In 0 In 1 3-wire 2-wire In 2 In 3 Prox Prox Prox Prox 41969A V = 12/24V dc C = Common Input Terminal Common Terminal Power Channel 0 Channel 1 Channel 2 Channel 3 Connect power on 3-wire proximity switches.
  • Page 37 Install POINT I/O Modules When you connect or disconnect wiring while field side power WARNING is on, an electrical arc can occur. This could cause an explosion in hazardous location installations. Be sure that power is removed or the area is nonhazardous before proceeding.
  • Page 38: 1734-Ob2E, 1734-Ob4E, 1734-Ob8E, 1734-Ob2, 1734-Ob4, And 1734-Ob8 Protected Output Modules

    Install POINT I/O Modules 1734-OB2E, 1734-OB4E, 1734-OB8E, 1734-OB2, 1734-OB4, and 1734-OB8 Protected Output Modules 1734-OB2E 1734-OB8E 1734-OB4E Module Status Module Module Status Status Module Status Network Network Status Network Status Status Network NODE: Status NODE: NODE: 24VDC 24VDC Source Source 24VDC Output Output...
  • Page 39 Install POINT I/O Modules 1734-OB2 and 1734-OB2E Module Wiring Diagram Out 1 Out 0 Load Load Out 0 Out 1 V = 12/24V dc, C = Common 44338 Field power is supplied from internal power bus Output Terminal Common Terminal Power Channel 0 0, 2...
  • Page 40 Install POINT I/O Modules 1734-OB8 and 1734-OB8E Module Wiring Diagram Load Load Out 0 Out 1 Load Load Out 3 Out 2 Load Load Out 4 Out 5 Load Load Out 6 Out 7 Common must be daisychained from a 1734 adapter, 1734-FPD module, 1734-EP24DC 42015 power supply, or from a user-supplied auxiliary terminal block.
  • Page 41: Ob2Ep Protected Output Modules

    Install POINT I/O Modules 1734-OB2EP Protected Output Module Module Status Module Status Network Status Network Status NODE: Protected Sourcing Output Status of Output 0 Status of Output 1 1734 OB2EP Output 1 Output 0 Connection Connection Output 1 Output 0 Connection Connection C = Common...
  • Page 42: 1734-Ow2 And 1734-Ow4 Relay Output Modules

    Install POINT I/O Modules 1734-OW2 and 1734-OW4 Relay Output Modules 1734-OW2 1734-OW4 Module Status Module Module Status Status Network Status Network Network Status Status NODE: NODE: Relay Relay Output Output Status of Output 0 Status of Output 1 Status of Output 2 Status of Output 3 1734 1734...
  • Page 43: 1734-Ow2 Modules With Load Powered By External Power Wiring

    Install POINT I/O Modules Channel Output Common Supply Supply voltage can range from +5V dc…240V ac, depending on relay load. Power for the module can be provided by the internal power bus. 1734-OW2 Modules with Load Powered by External Power Wiring Diagram Power Power...
  • Page 44: 1734-Ow4 Modules With Load Powered By External Power Wiring

    Install POINT I/O Modules 1734-OW4 Modules with Load Powered by External Power Wiring Diagram Power Power Supply Out 1A Out 0A Supply Load Load Out 0B Out 1B Power Power Out 2A Out 3A Supply Supply Out 3B Out 2B Load Load Out = Output channel relay contacts...
  • Page 45 Install POINT I/O Modules Do not attempt to increase load current or wattage capability ATTENTION beyond the maximum rating by connecting two or more outputs in parallel. The slightest variation in relay switching time may cause one relay to momentarily switch the total load current.
  • Page 46 Install POINT I/O Modules Relay Modules Using a 1734-FPD or 1734-EPAC Module to Create a New ac Power Bus IB2 IV2 IB4 IV4 EPAC OW2 OW2 OW2 IB2 IV2 IB4 IV4 FPD OW2 OW2 OW2 Power Power Power Power 120V ac 120V ac Relay Modules Using External Wiring for ac Power IB4 IV2...
  • Page 47: 1734-Ov2E, 1734-Ov4E, And 1734-Ov8E Sink Output Modules

    Install POINT I/O Modules 1734-OV2E, 1734-OV4E, and 1734-OV8E Sink Output Modules 1734-OV2E 1734-OV4E 1734-OV8E Module Status Module Module Module Status Status Status Network Status Network Network Network Status Status Status NODE: NODE: NODE: Status of Output 0 & 4 Status of Output 0 24VDC 24VDC 24VDC...
  • Page 48 Install POINT I/O Modules dc Sink Output Module Cat. No. 1734-OV4E Wiring Diagram Out 0 Out 1 Out 2 Out 3 Load Load Load Load V = 12/24V dc, C = Common 42015 Field power is supplied from internal power bus dc Sink Output Module Cat.
  • Page 49: 1734-Ox2 2-Relay Output Modules

    Install POINT I/O Modules 1734-OX2 2-relay Output Modules Module Status Network Status Status of Output 0 Status of Output 1 NC = Normally closed NO = Normally open RC = Relay Common +V = Positive Supply Output 0 Connection - NC NC - Output 1 Connection Output 0 Connection - NO NO - Output 1 Connection...
  • Page 50: Wiring Diagram

    Install POINT I/O Modules 734-OX2 Module with Load Powered by Internal Power Bus Wiring Diagram Out 1 Out 0 Out 1 Out 0 Load Out 0 Out 1 Load L2/N L2/N NC = Normally closed NO = Normally open RC = Relay Common 42019OX +V = Positive Supply Channel...
  • Page 51 Install POINT I/O Modules Do not attempt to increase load current or wattage capability ATTENTION beyond the maximum rating by connecting two or more outputs in parallel. The slightest variation in relay switching time may cause one relay to momentarily switch the total load current.
  • Page 52 Install POINT I/O Modules Wire with ac Modules Only Using a 1734-AENT Module, or Using a 1734-AENT Module to Create a New ac Power Bus AENT AENT IB2 IV4 FPD OX2 OX2 OX2 0 1 0 1 120V ac or 240V ac Based on I/O Modules 24V dc 24V dc AENT...
  • Page 53: 1734-Ia2 And 1734-Ia4 120 V Ac Input Modules

    Install POINT I/O Modules Wire Using External Power Source for ac Relay Power IB2 IB4 IV2 IV4 OX2OX2 OX2 42010lt L2/N 120V/240V ac 1734-IA2 and 1734-IA4 120 V ac Input Modules 1734-IA4 1734-IA2 Module Status Module Status Network Module Status Module Status Status Network...
  • Page 54: 1734-Im2 And 1734-Im4 220V Ac Input Modules

    Install POINT I/O Modules 1734-IA2 120 V ac Input Module Wiring Diagram 1734-IA4 120 V ac Input Module Wiring Diagram Ch 1 Ch 0 Prox Prox Prox Prox L2/N 44336 L2/N Ch0 = Channel 0 Input Ch1 = Channel 1 Input Ch2 = Channel 2 Input Ch3 = Channel 3 Input L2/N = 120V ac Neutral...
  • Page 55: 1734-Im2 120V Ac 2 Input Module Wiring Diagram

    Install POINT I/O Modules 1734-IM4 1734-IM2 Module Status Module Status Module Module Status Status Network Status Network Status Network Status Network Status NODE: NODE: 220VAC Input 220VAC Input Status of Input 0 Status of Input 0 Status of Input 1 Status of Input 1 Status of Input 2 Status of Input 3...
  • Page 56 Install POINT I/O Modules Ch 1 Ch 0 Prox Prox Prox Prox L2/N 44336 L2/N Ch0 = Channel 0 Input Ch1 = Channel 1 Input Ch2 = Channel 2 Input Ch3 = Channel 3 Input L2/N = 120V ac Neutral L1 = 120V ac Channel Input Terminal...
  • Page 57: 1734-Oa2 And 1734- Oa4 120/220V Ac Output Modules

    Install POINT I/O Modules 1734-OA2 and 1734- OA4 120/220V ac Output Modules 1734-OA2 1734-OA4 Status of Input 0 Module Status Module Status Status of Input 1 Module Module Status Network Status Status Network Status Network Network Status Status NODE: NODE: NODE: 120VAC 120/220VAC...
  • Page 58: 1734-Oa4 Ac 2 Output Module Wiring Diagram

    Install POINT I/O Modules 1734-OA4 ac 2 Output Module Wiring Diagram Ch 1 Ch 0 Ch 2 Ch 3 Load Load Load Load L2/N L2/N L2/N L2/N L1 =120/220V ac Supply 44399 L2/N = 120/220V ac Return Ch 0 = Channel 0 Ch 2 = Channel 2 Ch 1 = Channel 1 Ch 3 = Channel 3...
  • Page 59: Wiring Analog Modules

    Install POINT I/O Modules Wiring Analog Modules 1734-IE2C Analog Current Input Module Module Status Module Status Network Status Network Status NODE: 4-20mA Analog Status of Input 0 Input Status of Input 1 1734 IE2C Input 1 Connection Input 0 Connection Chas Gnd Chas Gnd Chas Gnd = Chassis ground...
  • Page 60: 1734-Ie2V Analog Voltage Input Module

    Install POINT I/O Modules 1734-IE2V Analog Voltage Input Module Module Status Module Status Network Status Network Status NODE: Analog Voltage Input Status of Input 0 Status of Input 1 1734 IE2V Input 1 Connection Input 0 Connection Chas Gnd Chas Gnd 41974 Chas Gnd = Chassis ground C = Common...
  • Page 61: 1734-Oe2C Analog Current Output Module

    Install POINT I/O Modules 1734-OE2C Analog Current Output Module Module Status Module Status Network Status Network Status NODE: 4-20mA Analog Output Status of Output 0 Status of Output 1 1734 OE2C Output 1 Connection Output 0 Connection Chas Gnd Chas Gnd ChasGnd = Chassis ground 41974 C = Common...
  • Page 62: 1734-Oe2V Analog Voltage Output Module

    Install POINT I/O Modules 1734-OE2V Analog Voltage Output Module Module Status Module Status Network Status Network Status NODE: Analog Voltage Output Status of Output 0 Status of Output 1 1734 OE2V Output 1 Connection Output 0 Connection Chas Gnd Chas Gnd Chas Gnd = Chassis ground C = Common 41974...
  • Page 63: Wiring Power Distribution And Other Modules

    Install POINT I/O Modules Wiring Power Distribution 1734-PDN Communication Interface Module and Other Modules DeviceNet Connector System Power DeviceNet Power CHAS GND CHAS GND NC = No Connection CHAS GND = Chassis Ground 41970 C = Common V = Supply 1734-PDN Module Wiring Diagram CHAS CHAS...
  • Page 64 Install POINT I/O Modules Black DeviceNet CAN - Low Blue connection Shield Bare White CAN - High Wire the Communication Interface Module for ac Modules Only ac Power Bus 120V ac Publication 1734-UM001D-EN-P - April 2008...
  • Page 65: 1734-Fpd Field Potential Distributor Module

    Install POINT I/O Modules 1734-FPD Field Potential Distributor Module CHAS GND CHAS GND 41970 NC = No Connection CHAS GND = Chassis Ground C = Common V = Supply 1734-FPD Modules for 12/24V dc Wiring Diagram CHAS CHAS V dc This supply will be connected to the internal power bus.
  • Page 66 Install POINT I/O Modules 1734-FPD Modules for 120/240V ac Wiring Diagram CHAS CHAS L2/N L2/N V ac This supply will be connected to the internal power bus. L2/N = Neutral, L1 = 120/240V ac CHAS GND = Chassis ground Connect Terminal L2/N Chas Gnd...
  • Page 67 Install POINT I/O Modules Wiring Using a 1734-FPD Module to Create a New dc Power Bus This configuration changes power bus voltage for 12/24V dc systems. FPD IB2 IB4 IV2 PDN IB2 IB4 OB2E OB4E OB4E 12V dc Digital I/O Digital I/O 42009dc Power Bus...
  • Page 68: 1734-Ep24Dc Expansion Power Supply

    Install POINT I/O Modules 1734-EP24DC Expansion Power Supply 1734-EP24DC System Power Field Power CHAS GND CHAS GND NC = No Connection CHAS GND = Chassis Ground C = Common V = Supply 41970 12/24v dc Wiring Diagram Use the 1734-EP24DC expansion power supply only with ATTENTION adapter class products.
  • Page 69 Install POINT I/O Modules Connect Terminal Terminals (for continuing power) +V dc -V dc Chas Gnd 12/24V dc becomes the internal power bus for modules to the right. Example of Continuing Power EP24DC 1734adn4 12/24V dc only Example of continued power. The 1734-EP24DC expansion power supply can be used with IMPORTANT POINT I/O adapters only.
  • Page 70 Install POINT I/O Modules Example of Functional Partitioning EP24DC 12/24V dc Analog Supply 12/24V dc 1734adn4A Digital Supply Publication 1734-UM001D-EN-P - April 2008...
  • Page 71: 1734-Epac Ac Expansion Power Supply

    Install POINT I/O Modules Example of Logical Partitioning EP24DC 12V dc Supply 1734adn4A 24V dc Supply 1734-EPAC ac Expansion Power Supply NC = No Connection PE = Protective Earth Ground L2/N L2/N L2/N = Neutral L1 = 120/240V ac 41970 Publication 1734-UM001D-EN-P - April 2008...
  • Page 72: 120/240V Ac Wiring Diagram

    Install POINT I/O Modules 120/240V ac Wiring Diagram If you connect or disconnect wiring while field side power is on, ATTENTION an electrical arc can occur. This could cause an explosion in hazardous location installations. Be sure that power is removed or the area is nonhazardous before proceeding.
  • Page 73 Install POINT I/O Modules Example of Functional Partitioning 1734-EPAC 1734-EPAC 1734-ADN Adapter Status DeviceNet Status PointBus Status 1734-EPAC 1734-EPAC 1734-ADN System System Power System Power Power Field Field Power Power DeviceNet Power 0 1 0 1 0 1 0 1 41970C 240V ac Supply 120V ac Supply...
  • Page 74: 1734-Arm Address Reserve Module

    Install POINT I/O Modules 1734-ARM Address Reserve Module The 1734-ARM module requires no external wiring. NC = No connection 41974 1734-CTM and 1734-VTM Modules 1734-CTM 1734-VTM 1734 1734 Voltage Out Voltage Out Common Common Voltage Out Voltage Out Common Common Voltage Out Voltage Out Common...
  • Page 75: Sink Input Wiring Diagram

    Install POINT I/O Modules Sink Input Wiring Diagram 1734-CTM 1734-VTM 1734-IB8 2-wire Prox In 0 In 1 In 2 In 3 In 4 In 5 3-wire Prox In 6 In 7 C = Common V = Voltage Out 43927 Source Input Wiring Diagram 1734-VTM 1734-CTM 1734-IV8...
  • Page 76: Source Output Wiring Diagram

    Install POINT I/O Modules Source Output Wiring Diagram 1734-CTM 1734-OB8 Load Out 0 Out 1 Load Out 2 Out 3 C = Common Load Out 5 Out 4 Load Out 6 Out 7 43928 Sink Output Wiring Diagram 1734-VTM 1734-OV8 Load Out 0 Out 1...
  • Page 77 Install POINT I/O Modules Publication 1734-UM001D-EN-P - April 2008...
  • Page 78 Install POINT I/O Modules Publication 1734-UM001D-EN-P - April 2008...
  • Page 79: Install Pointblock I/O Modules

    Chapter Install POINTBlock I/O Modules Read this chapter for information about how to wire POINTBlock I/O About This Chapter modules to include the following: • 1734D-IB8XOB8 POINTBlock 8 dc In/8 dc Out Modules • 1734D-IB8XOW8 POINTBlock 8 dc In/8 Relay Out Modules •...
  • Page 80: Wiring Pointblock Modules

    Install POINTBlock I/O Modules Wiring POINTBlock 1734D-IB8XOB8 POINTBlock 8 dc In/8 dc Out Modules Modules Module Status Network Status Inputs Outputs I/O status 10-60 1’s Node Address Rotary Switch 10’s Node Address Rotary Switch 42004 8 Input/8 Output Module Wiring Diagram Field 12/24V dc Power...
  • Page 81: Sink Input Wiring Diagram

    Install POINTBlock I/O Modules Sink Input Wiring Diagram In 0 In 1 2-wire 3-wire In 2 In 3 Prox Prox Prox Prox 41967 V = 12/24V dc C = Common Channel Input Terminal Common Voltage Remote Termination Block 1 Remote Termination Block 2 Connect common on 3-wire proximity switches.
  • Page 82: Output Wiring Diagram

    Install POINTBlock I/O Modules Output Wiring Diagram Out 0 Out 1 Out 2 Out 3 Load Load Load Load 42015 V = 12/24V dc, C = Common Field power is supplied from internal power bus Output Terminal Common Terminal Power Remote Termination Block 3 Channel 0 Channel 1...
  • Page 83 Install POINTBlock I/O Modules Latch Mode Functionality State Indication Error Bit Dark Yellow Faulted/On Faulted/Off Flashing Red To reset an output, the reset bit for the output can be set, or the output bit must be cycled off/on. Auto Retry Mode Functionality State Indication Error Bit...
  • Page 84: Input/8 Relay Output Module Wiring Diagram

    Install POINTBlock I/O Modules 1734D-IB8XOW8 POINTBlock 8 dc In/8 Relay Out Modules Module Status Network Status Inputs Outputs I/O status 10-60 1’s Node Address Rotary Switch 10’s Node Address Rotary Switch 42004 8 Input/8 Relay Output Module Wiring Diagram 12/24V dc Field Power Inputs Outputs...
  • Page 85 Install POINTBlock I/O Modules Channel Input Terminal Common Voltage Remote Termination Block 1 Remote Termination Block 2 Connect common on 3-wire proximity switches. 12/24V dc is supplied through the internal power bus. When connecting more then one wire in a termination point, ATTENTION make sure that both wires are the same gauge and type.
  • Page 86 Install POINTBlock I/O Modules Output Wiring Diagram (Load Powered by External Power) Power Power Supply Supply Load Load Out = Output channel relay contacts Power Supply = can range from +5V dc to 240V ac C = Common Channel Output Common Supply Remote Termination Block 3...
  • Page 87: 1734D-Ia8Xoa8 Pointblock 8 Ac In/8 Ac Out Modules

    Install POINTBlock I/O Modules DeviceNet Connector Wiring DeviceNet CAN - High White Connection Bare Shield CAN - Low Blue Black 42132 1734D-IA8XOA8 POINTBlock 8 ac In/8 ac Out Modules Module Status Network Status Inputs Outputs I/O status 10-60 1’s Node Address Rotary Switch 10’s Node Address Rotary Switch 42004 1734D-IA8XOA8 POINTBlock 8 ac In/8 ac Out Modules Wiring...
  • Page 88: Input Wiring Diagram

    Install POINTBlock I/O Modules Input Wiring Diagram In 0 In 1 In 2 In 3 Prox Prox 41967ac L1 = 120V ac L2 = Return Channel Input Terminal Return Voltage Remote Termination Block 1 Remote Termination Block 2 120V ac is supplied through the internal power bus. When connecting more then one wire in a termination point, ATTENTION make sure that both wires are the same gauge and type.
  • Page 89: Output Wiring Diagram

    Install POINTBlock I/O Modules Output Wiring Diagram In 0 In 1 In 2 In 3 Load Load Load Load 41967ac L1 = 120V ac Output Terminal Common Terminal Power Remote Termination Block 3 Channel 0 Channel 1 Channel 2 Channel 3 Remote Termination Block 4 Channel 4 Channel 5...
  • Page 90: Out Modules

    Install POINTBlock I/O Modules 1734D-IA8XOW8 POINTBlock 8 ac In/8 Relay Out Modules Module Status Network Status Inputs Outputs I/O status 10-60 1’s Node Address Rotary Switch 10’s Node Address Rotary Switch 42004 1734D-IA8XOW8 POINTBlock 8 ac In/8 Relay Out Modules Wiring Diagram 120V ac Field Power...
  • Page 91: Input Wiring Diagram

    Install POINTBlock I/O Modules Input Wiring Diagram In 1 In 0 In 3 In 2 Prox Prox 41967ac L1 = 120V ac L2 = Return Channel Input Terminal Return Voltage Remote Termination Block 1 Remote Termination Block 2 120V ac is supplied through the internal power bus. When connecting more then one wire in a termination point, ATTENTION make sure that both wires are the same gauge and type.
  • Page 92: Output Wiring Diagram

    Install POINTBlock I/O Modules Output Wiring Diagram Load Powered by External Power Power Power Out 0A Out 1A Supply Supply Out 0B Out 1B Out 2A Out 3A Load Load Out = Output channel relay contacts Out 2B Out 3B L1 = 120V ac L2 = Return Channel...
  • Page 93: 1734D-Ia16 Pointblock 16 Ac Input Modules

    Install POINTBlock I/O Modules DeviceNet Connector Wiring DeviceNet CAN - High White Connection Bare Shield CAN - Low Blue Black 42132 1734D-IA16 POINTBlock 16 ac Input Modules Module Status Network Status I/O Status 1’s Node Address Rotary Switch 10’s Node Address Rotary Switch 42004 Wire the 16 ac Input Module Wiring Diagram 120V ac...
  • Page 94: Input Wiring Diagram

    Install POINTBlock I/O Modules Input Wiring Diagram RTB 1 In 0 In 1 In 2 In 3 Prox Prox L1 = 120V ac 41967ac L2 = Return Repeat for RTB 2, 3 and 4 When connecting more then one wire in a termination point, ATTENTION make sure that both wires are the same gauge and type.
  • Page 95 Install POINTBlock I/O Modules Channel Input Terminal Return Voltage Remote Termination Block 0 Field Power Block Vin (L1) 6 and/or 7 Return (L2/N) 4 and/or 5 Remote Termination Block 1 Remote Termination Block 2 Remote Termination Block 3 Remote Termination Block 4 120V ac is supplied through the internal power bus.
  • Page 96: 1734D-Ib16 Pointblock 16 Dc Input Modules

    Install POINTBlock I/O Modules DeviceNet Connector Wiring DeviceNet White CAN - High Connection Bare Shield CAN - Low Blue 42132 Black 1734D-IB16 POINTBlock 16 dc Input Modules Module Status Network Status I/O status 10’s Node Address Rotary Switch 1’s Node Address Rotary Switch 42004 Publication 1734-UM001D-EN-P - April 2008...
  • Page 97: 16 Dc Input Module Wiring Diagram

    Install POINTBlock I/O Modules 16 dc Input Module Wiring Diagram Field 12/24V dc NC = Power Inputs No Connection C = Common Chas Gnd = Chassis Ground V = Supply V dc 42064 RTB 0 RTB 1 RTB 2 RTB 3 RTB 4 This supply will be connected to the internal power bus.
  • Page 98 Install POINTBlock I/O Modules Channel Input Terminal Common Voltage Remote Termination Block 0 Field Power Block Vin (supply) 6 and 7 Common) 4 and 5 Remote Termination Block 1 Remote Termination Block 2 Remote Termination Block 3 Remote Termination Block 4 Connect common on 3-wire proximity switches.
  • Page 99: Point I/O Module Data

    Chapter POINT I/O Module Data Read this chapter for information about module status, input, output, and About This Chapter configuration data, and default data maps for POINT I/O modules to include the following: • Digital Input Modules • Digital Output Modules •...
  • Page 100 POINT I/O Module Data Default Data Map for the 1734-IB2 and 1734-IV2 Input Modules Message Size: 1 Byte Produces (scanner Rx) Not used Consumes (scanner Tx) No consumed data Where: Ch0 = input channel 0, Ch1 = input channel 1, 0 = off, 1 = on Default Data Map for the 1734-IB4 and 1734-IV4 Input Modules Message Size: 1 Byte Produces (scanner Rx)
  • Page 101: Digital Ac Input Modules

    POINT I/O Module Data Default Data Map for 1734-IB4D Module - - Configuration Assembly Instance 103 Message Size: 18 Bytes Consume 0 Input 0 Off to On Filter Byte 0 Consume 1 Input 0 Off to On Filter Byte 1 Consume 2 Input 0 On to Off Filter Byte 0 Consume 3...
  • Page 102: Digital Output Modules

    POINT I/O Module Data I/O messages are sent to (consumed) and received from (produced) these POINT I/O modules. These messages are mapped into the processor memory. These POINT I/O modules produce one byte of input data (scanner Rx). They do not consume I/O data (scanner Tx). Default Data Map for the 1734-IA2 and 1734-IM2 Input Modules Message Size: 1 Byte Produces (scanner Rx)
  • Page 103 POINT I/O Module Data Default Data Map for 1734-OB2, 1734-OB2E, and 1734-OV2E Output Module Message Size: 1 Byte Produces Not used Channel status (scanner Rx) (1734-OB2E module only) Where: 0 = no error, 1 = error Message Size: 1 Byte Consumes Not used Channel state...
  • Page 104: Digital Ac Output Modules

    POINT I/O Module Data Default Data Map for the 1734-OB2EP Output Module Message Size: 1 Byte Produces Not used Channel status (scanner Rx) Where: 0 = no error, 1 = error Message Size: 1 Byte Consumes Not used Channel state (scanner Tx) Where: 0 = Off, 1 = On...
  • Page 105: Relay Output Modules

    POINT I/O Module Data The relay output modules consist of 1734-OW2 and 1734-OW4 2-relay output Relay Output Modules modules and 1734-OX2 4-relay output modules. Features of the 1734-OW2 and 1734-OW4 relay modules include the following: • Type A Normally Open relays •...
  • Page 106: Analog Input Modules

    POINT I/O Module Data Default Data Map for the 1734-OX2 Relay Output Module Message Size: 1 Byte Produces No produced data (scanner Rx) Consumes Not used Ch1 Ch0 Channel state (scanner Tx) Where: 0 = NO contact off, NC contact on 1 = NO contact on, NC contact off The 1734-IE2C Analog Input Module is a two-channel module that converts Analog Input Modules...
  • Page 107: Data

    POINT I/O Module Data Data The1734-IE2C module operates in unipolar mode only; the 1734-IE2V module operates in unipolar or bipolar modes. Data returned from the module is scaled by the user to any 16-bit signed integer (–32,768…+32,767). Six bytes of data are read from the 1734-IE2C and 1734-IE2V modules. No data is written to the input modules.
  • Page 108 POINT I/O Module Data Default Data Map for the 1734-IE2V Analog Input Module Produces (scanner Rx) Input Channel 0 - High Byte Input Channel 0 - Low Byte Input Channel 1 - High Byte Input Channel 1 - Low Byte Status Byte for Channel 1 Status Byte for Channel 0 HHA LLA...
  • Page 109: Scaling

    POINT I/O Module Data Scaling Select scaling for each channel by making the selection on the configuration dialog. Scaling is the conversion of unscaled data to engineering units. The high and low scalers (Engineering Units) are signed integers. There are no restrictions on these units.
  • Page 110: Latch Alarms

    POINT I/O Module Data • Low Low Alarm Value Bit - When the input signal is less then the Low Low Alarm value, this bit (Channel Status Bit 4) is set. The default value for this alarm is as follows: •...
  • Page 111: Digital Filter

    POINT I/O Module Data Digital Filter A digital filter is available on the input modules. You set a time constant that is used in the equation: Yn = Yn-1 + (dt / (dt + T ) * (Xn-Yn-1) Where: Yn = new data Yn-1 = old data.
  • Page 112: Alarms

    POINT I/O Module Data Alarms Available alarms include the following: • Low • Low Low • High • High High Each alarm has one status bit which is set to indicate when the input goes beyond its set point. All Alarm Status bits can be read individually or from the Channel Status Byte (bits 2…5).
  • Page 113: Channel Indicator Behavior

    POINT I/O Module Data Channel Indicator Behavior See the table for a listing of channel indicator states for given module conditions. Indication Probable Cause Channel Status Module in CAL mode Solid green Normal (channel scanning inputs) Flashing green Channel being calibrated Solid red No power or major channel fault Flashing red...
  • Page 114 POINT I/O Module Data Default Data Map for the 1734-OE2C Analog Output Module Message Size: 4 Bytes Consumes (Tx) Output Channel 0 High Byte Output Channel 0 Low Byte Output Channel 1 High Byte Output Channel 1 Low Byte Message Size: 2 Bytes Produces (Rx) High Byte - Channel 1 Status Low Byte - Channel 0 Status...
  • Page 115: Operational Modes

    POINT I/O Module Data Operational Modes The 1734-OE2C module has these modes: • 0…20 mA • 4…20 mA (Default mode) The 1734-OE2V module has these modes: • 0… 10V dc (Default mode) • -10…10V dc You can set Channel Mode individually. The effective difference in the two modes is how you apply the scalers.
  • Page 116: Fault And Idle/Program Mode Action

    POINT I/O Module Data Since scalers have no restrictions, use care when configuring the module. If the lower scaler is set to –32,768 and the module is in 4…20 mA (or -10V…10V) mode, the module is incapable of setting the output to 0 mA (or less than -10V on the 1734-OE2V module) because that requires a number smaller than –32,768.
  • Page 117: Channel Status

    POINT I/O Module Data Channel Status The module status bits included in each Channel Status Byte are the following: • Channel Fault • CAL Mode • Low Clamp • High Clamp Channel Status can be read individually using RSNetWorx software or by reading the Channel Status Byte in the Module Produce Assembly.
  • Page 118: Low And High Clamps

    POINT I/O Module Data Low and High Clamps The clamps define the maximum and minimum values of the output. These default to the following with the data scaled: • -32,768 counts (0 or 4 mA) and +32,767 counts (21 mA) for the 1734-OE2C module •...
  • Page 119: Channel Indicators

    POINT I/O Module Data Channel Indicators See the table for channel indicator states for given module condition. Indication 1734-OE2C Probable Cause 1734-OE2V Probable Cause Channel Status Module in CAL mode Module in CAL mode Solid green Channel actively controlling outputs Channel actively controlling outputs Blinking green Channel calibrating...
  • Page 120 POINT I/O Module Data POINTBus Expansion DeviceNet Port Connector to 5V Microprocessor Field Bus Connector I/O Circuits Power I/O Connections Connections 120V ac or 24V dc 41971 Whatever field power you supply is connected to the ATTENTION internal field-power bus. For example, if 120V ac is applied to the power connections, there will be 120V ac applied to the modules through the internal field-power bus.
  • Page 121 POINT I/O Module Data Default Data Map for the 1734D-IB8XOB8E dc Input/Output Module Consumes Ch7 Ch6 Output Data (or (scanner Tx) state) Where: 0 = off, 1 = on The 1734D-IB8XOW8 module produces one byte of input data (scanner Rx) status.
  • Page 122 POINT I/O Module Data The 1734D-IA8XOW8 module produces one byte of input data (scanner Rx) status) It consumes one byte of output data (scanner Tx). Default Data Map for the 1734D-IA8XOW8 ac Input/Relay Output Module Message Size: 1 Byte Produces Ch7 Ch6 Input Data (scanner Rx)
  • Page 123: Calibrate Your Analog Modules

    Chapter Calibrate Your Analog Modules Read this chapter for information about how to calibrate analog modules. Your About This Chapter analog I/O module is factory-calibrated. You may choose to recalibrate your module in your system to increase its accuracy for your specific application. This chapter covers the following: •...
  • Page 124: Tools Required To Calibrate Your Analog Modules

    Calibrate Your Analog Modules To maintain your module’s accuracy specifications, we recommend you use Tools Required to Calibrate calibration instruments with specific ranges. See the table for a list of the Your Analog Modules recommended instruments for each module. Module Recommended Instrument Range 1.00…20.00 mA (+/-0.15 μA) current source 1734-IE2C...
  • Page 125: Calibrate The Analog Current Input Module

    Calibrate Your Analog Modules To calibrate your current input module, connect the module in a system Calibrate the Analog similar to that shown in the figure. Current Input Module Apply power to the power supply and module for at least 10 IMPORTANT minutes before calibrating the module.
  • Page 126 Calibrate Your Analog Modules 1. Double-click the icon to bring up the General parameter dialog. The EDS editor asks you if you want to upload the configuration from the device. 2. From the EDS editor, click Upload 3. From the General parameter dialog, click Device Parameters. You see the Device Parameters dialog.
  • Page 127 Calibrate Your Analog Modules 6. Click the Download to Device button. Both channel status indicators turn off. Leave on single. 7. Click Calibration Channel Set to bring up channel selections, and select a channel. 8. Click the Download to Device button. 9.
  • Page 128 Calibrate Your Analog Modules 11. From the Device Parameters dialog, click the Download to Device button. The status indicator for the channel being calibrated blinks. 12. Set the current source to 20 mA. 13. Click Accept High Calibration. 14. Click the Download to Device button. Calibration is complete as soon as High and Low calibration for the selected channels are done successfully.
  • Page 129: Calibrate The Analog Current Output Module

    Calibrate Your Analog Modules To calibrate your output module, connect the module in a DeviceNet system Calibrate the Analog similar to that shown in the figure, and use this procedure. Current Output Module Apply power to the power supply and module for at least 10 IMPORTANT minutes before calibrating the module.
  • Page 130 Calibrate Your Analog Modules You see the EDS editor ask you if you want to upload the configuration from the device. 2. From the EDS editor dialog, click Upload. 3. Click Device Parameters. You see the Device Parameters dialog. 4. Select Calibration at the Group pull-down. Group pull-down 5.
  • Page 131 Calibrate Your Analog Modules 6. From the Device Parameters dialog, click the Download to Device button. 7. Click Calibration Channel Sel to bring up channel selections, and select a channel. 8. Click the Download to Device button. 9. Select Output Low Reference, and download to the module. Publication 1734-UM001D-EN-P - April 2008...
  • Page 132 Calibrate Your Analog Modules The selected channel status indicator blinks green. 10. Enter the value shown on your DVM for the Channel Low Value (4.044 in the example). Publication 1734-UM001D-EN-P - April 2008...
  • Page 133 Calibrate Your Analog Modules 11. From the Device Parameters dialog, select the Output High Value, and download to the module. 12. From the Device Parameters dialog, enter the value shown on the DVM, which is 20.231 in this example. 13. Repeat these steps for the other channel. 14.
  • Page 134: Calibrate The Analog Voltage Input Module

    Calibrate Your Analog Modules You see the EDS Editor and are prompted to download to the module. 16. From the EDS Editor dialog, click Yes. If calibration was accomplished, the Cal Status reflects good. Your module is now calibrated. To calibrate your voltage input module, connect the module in a DeviceNet Calibrate the Analog system similar to that shown in the figure.
  • Page 135 Calibrate Your Analog Modules You can calibrate both voltage input channels at the same time using one voltage source. DeviceNet Input Channel 0 Connect to 0 and 4 Channel 1 Connect to 1 and 5 Power Supply Voltage 4032 250 Ω Voltage Source 1.
  • Page 136 Calibrate Your Analog Modules 4. From the General Parameters dialog, select Calibration at the Groups pull-down. This is the group pull-down. 5. Select your channel. 6. Click Calibration Command, and Apply. 7. Click the Download to Device button. Both channel status indicators turn off. 8.
  • Page 137 Calibrate Your Analog Modules 10. Click the Download to Device button. The status indicator for the channel being calibrated blinks. 11. Set the voltage source to +10.0V. 12. Click Accept High Calibration. 13. Click the Download to Device button. Calibration is complete as soon as High and Low calibration for the selected channels are done successfully.
  • Page 138: Calibrate The Analog Voltage Output Module

    Calibrate Your Analog Modules To calibrate your output module, connect the module in a DeviceNet system Calibrate the Analog similar to that shown in the figure and use this procedure. Voltage Output Module Apply power to the power supply and module for at least 10 IMPORTANT minutes before calibrating the module.
  • Page 139 Calibrate Your Analog Modules 2. From the EDS Editor dialog, click Upload. 3. From the Device Parameters dialog, select Calibration at the Groups pull-down. Groups pull-down Click Calibration. 4. Select your channel(s). Publication 1734-UM001D-EN-P - April 2008...
  • Page 140 Calibrate Your Analog Modules 5. Click Calibration Command and Apply. 6. Click the Download to Device button. The channel status indicator turns off. 7. Select a channel. 8. Click the Download to Device button. 9. Select Output Low Reference and download to the module. The selected channel status indicator blinks green.
  • Page 141 Calibrate Your Analog Modules 10. Enter the value shown on your DVM for the Channel Low Value (-10.1234 in the example). Type in the resulting value from your DVM. 11. Select the Output High Value and download to the module. 12.
  • Page 142 Calibrate Your Analog Modules 14. From the Device Parameters dialog, select All, and click Finish Calibration to complete the calibration process. You see the EDS Editor dialog that prompts you to download to the module. 15. From the EDS Editor dialog, click Yes. If calibration was accomplished, the Cal Status reflects good.
  • Page 143: Troubleshoot With The Indicators

    Chapter Troubleshoot with the Indicators Read this chapter for information about troubleshooting with the following About This Chapter indicators: • Module status • Network status • Power indication • Calibration status • I/O POINT status (ON/OFF/fault or diagnostic) Refer to each module’s individual indicators for detailed information. About Module Diagnostics All status and diagnostic information (strobed, polled, cyclic, or change-of-state) is reported back over the network communication adapter.
  • Page 144: Network And Module Status Indications

    Troubleshoot with the Indicators Network and Module Status Indications The network and module status indications are the same for all modules. Module Status Module Status Network Status NODE: Network Status 24VDC Sink Input Publication 1734-UM001D-EN-P - April 2008...
  • Page 145 Troubleshoot with the Indicators Indication Probable Cause Recommended Action Module Status No power applied to device. Apply power to device. Solid green Device is operating normally. None. Flashing green Device needs commissioning due to configuration Configure device properly. missing, incomplete, or incorrect. Flashing red Recoverable fault is present.
  • Page 146: Troubleshoot Digital Modules

    Troubleshoot with the Indicators The I/O status indicators provide input and output indications for each Troubleshoot Digital module. Individual meanings are indicted in the tables. Modules 1734-IB2, 1734-IB4, and 1734-IB8 Sink Input Modules 1734-IB4 1734-IB2 1734-IB8 Module Status Module Status Module Module Module...
  • Page 147 Troubleshoot with the Indicators 1734-OB2E, 1734-OB4E, and 1734-OB8E Source Output Modules 1734-OB2E 1734-OB4E 1734-OB8E Module Status Module Status Module Module Module Status Status Status Network Status Network Status Network Network Network Status Status Status NODE: NODE: NODE: 24VDC 24VDC 24VDC Source Source Source...
  • Page 148: 1734-Ob2Ep Protected Output Module

    Troubleshoot with the Indicators 1734-OB2EP Protected Output Module Module Status Module Status Network Status Network Status NODE: Protected Sourcing Output Status of Output 0 Status of Output 1 1734 OB2EP Indication Probable Cause Recommended Action I/O Status All outputs are inactive. None.
  • Page 149: 1734-Ov2E, 1734-Ov4E, And 1734-Ov8E Protected Sink Output

    Troubleshoot with the Indicators Indication Probable Cause Recommended Action I/O Status Input is in the off-state. None. Yellow Input is in the on-state. None. 1734-OV2E, 1734-OV4E, and 1734-OV8E Protected Sink Output Modules 1734-OV2E 1734-OV4E 1734-OV8 Module Status Module Status Module Module Module Status Module...
  • Page 150: 1734-Ow2 And 1734-Ow4 Relay Output Modules

    Troubleshoot with the Indicators 1734-OW2 and 1734-OW4 Relay Output Modules 1734-OW2 1734-OW4 Module Status Module Module Status Status Network Status Network Network Status Status NODE: NODE: Relay Relay Output Output Status of Output 0 Status of Output 1 Status of Output 2 Status of Output 3 1734 1734...
  • Page 151: 1734-Ox2 Relay Output Module

    Troubleshoot with the Indicators 1734-OX2 Relay Output Module Module Module Status Status Network Status Network Status NODE: Relay Output Status of Output 0 Status of Output 1 1734 Indication Probable Cause Recommended Action I/O Status Output is off. None. Yellow Output is on.
  • Page 152: 1734-Oa2 And 1734-Oa4 120/220V Ac Output Module

    Troubleshoot with the Indicators 1734-OA2 and 1734-OA4 120/220V ac Output Module 1734-OA2 1734-OA4 Module Status Module Status Network Status Network Status Status of Output 0 Status of Output 0 Status of Output 1 Status of Output 1 Status of Output 2 44209 44210 Status of Output 3...
  • Page 153: Troubleshoot Analog Modules

    Troubleshoot with the Indicators Each analog module has I/O indicators to show the status of the Troubleshoot Analog inputs/outputs. Refer to the individual module for I/O status information. Modules 1734-IE2C Analog Current Input Module Module Status Module Status Network Status Network Status NODE:...
  • Page 154: 1734-Oe2C Analog Current Output Module

    Troubleshoot with the Indicators 1734-OE2C Analog Current Output Module Module Status Module Status Network Status Network Status NODE: 4-20mA Analog Output Status of Output 0 Status of Output 1 1734 OE2C Indication Probable Cause Recommended Action Channel Status Module is in CAL mode. None.
  • Page 155: 1734-Oe2V Analog Voltage Output Module

    Troubleshoot with the Indicators 1734-OE2V Analog Voltage Output Module Module Status Module Status Network Status Network Status NODE: Analog Voltage Output Status of Output 0 Status of Output 1 1734 OE2V Indication Probable Cause Recommended Action Channel Status Module is in CAL mode. None.
  • Page 156: Troubleshoot I/O Communication Modules

    Troubleshoot with the Indicators The status indicators on the communication modules provide system power Troubleshoot I/O and DeviceNet power indications. Communication Modules 1734-PDN DeviceNet Communication Interface Module System Power DeviceNet Power Indicator Indication Probable Cause Recommended Action • Device is not active. System Power 1.
  • Page 157: 1734-Adn (X) Devicenet Adapter

    Troubleshoot with the Indicators 1734-ADN (X) DeviceNet Adapter 1734-ADN DeviceNet Adapter 1734-ADNX DeviceNet Adapter Adapter Status Adapter Status Adapter Adapter Status Status DeviceNet Status DeviceNet DeviceNet DeviceNet Status Status Status Subnet Status Subnet PointBus POINTBus Status Status Status (includes POINTBus status) 1734-ADNX 1734-ADN...
  • Page 158 Troubleshoot with the Indicators Indication Probable Cause Recommended Action Flashing red One or more I/O connections are in timed-out state Check for I/O module failure, and correct, as needed. Solid red Critical link failure present with failed communication device. Verify that adapter and terminal bases are Device detected error that prevents it from communicating on the properly installed, and reinstall, as needed.
  • Page 159: 1734-Acnr Controlnet Adapter

    Troubleshoot with the Indicators 1734-ACNR ControlNet Adapter Module Status Module Status POINTBus Status PointBus Status ControlNet A Status ControlNet A Status ControlNet B Status ControlNet B Status 1734-ACNR System Power System Power Field Power Field Power 43265 Indication Probable Cause Recommended Action Module Status No power applied to device.
  • Page 160 Troubleshoot with the Indicators Indication Probable Cause Recommended Action POINTBus Status Device not powered - check module status indicator. Apply power to device. Alternating LED power cycle test is present. None. red/green • Change chassis size to match Flashing red Recoverable fault has occurred: •...
  • Page 161 Troubleshoot with the Indicators Indication Probable Cause Recommended Action ControlNet A/B Status Viewed Together (A and B) Both Steady Off Reset, no power, or entire network interface deactivated. None or cycle power. Alternating Self test mode is present. None. red/green Alternating Incorrect configuration is present.
  • Page 162: 1734-Apb Profibus Adapter

    Troubleshoot with the Indicators 1734-APB PROFIBUS Adapter Adapter Adapter Status Status PROFIBUS PROFIBUS Status Status POINTBus Status PointBus Status 1734-APB System Power System Power Field Field Power 1734-2 Power Indication Probable Cause Recommended Action Adapter Status • No power supplied. 1.
  • Page 163 Troubleshoot with the Indicators Indication Probable Cause Recommended Action POINTBus Status • No power supplied. Apply power. • Hardware check is in progress. • Initialization is in progress. Solid green Normal operation present. None. Flashing red 1 Hz - Incorrect POINT I/O module installed. Verify module installation, no modules removed, POINT I/O module removed from backplane.
  • Page 164: 1734-Aent Ethernet/Ip Adapter

    Troubleshoot with the Indicators 1734-AENT EtherNet/IP Adapter Module Status Module Status Network Activity Network Activity Network Status Network Status POINTBus Status PointBus Status 1734-AENT System Power System Power Field Power Field Power 43248aent Indication Probable Cause Recommended Action Module Status No power applied to device Apply power to the device.
  • Page 165 Troubleshoot with the Indicators Indication Probable Cause Recommended Action Network Activity No link established. Verify network cabling, and correct, as needed. Flashing Transmit or receive activity present. None. green/Off Steady green Link established. None. Network Status Device not initialized. The module does not have an IP address. Apply power to device, verify IP address, and correct, as needed.
  • Page 166 Troubleshoot with the Indicators Indication Probable Cause Recommended Action POINTBus Status Device not powered - check module status indicator. Apply power to device. Flashing LED power cycle test present. None. red/green Flashing red Recoverable fault occurred: • At power cycle the number of expected modules •...
  • Page 167: About This Appendix

    Appendix Default Data Maps Read this appendix for a list of default data maps for About This Appendix 1734 POINT I/O modules. For the Default Data Map of See Page Digital Modules 1734-IB2 Sink Input Module 1734-IB4 Sink Input Module 1734-IB8 Sink Input Module 1734-IV2 Source Input Module 1734-IB4D Sink Input Modules with Diagnostics...
  • Page 168: Digital Module Default Data Maps

    Default Data Maps I/O messages are sent to (consumed) and received from (produced) the Digital Module Default POINT I/O modules. You map these messages into the processor memory. Data Maps 1734-IB2 Sink Input Module Message Size: 1 Byte Produces (scanner Rx) Consumes (scanner Tx) No consumed data Where: Ch0 = channel 0, Ch1 = channel 1;...
  • Page 169: 1734-Ib4D Sink Input Modules With Diagnostics

    Default Data Maps 1734-IB4D Sink Input Modules with Diagnostics Default Data Map - Produced Assembly Instance 101 Message Size: 2 Bytes Produce 0 (Rx) Fault 3 Fault 2 Fault 1 Fault 0 Input 3 Input 2 Input 1 Input 0 Produce 1 (Rx) SC 3 SC 2...
  • Page 170: 1734-Iv2 Source Input Module

    Default Data Maps Default Data Map - Configuration Assembly Instance 103 Message Size: 18 Bytes Consume 17 Produced Assembly Instance Produce (Tx) No produced data Where: OW = open wire. 1734-IV2 Source Input Module Message Size: 1 Byte Produces (scanner Rx) Consumes (scanner Tx) No consumed data Where: Ch 0 = input channel 0 data...
  • Page 171: 1734-Ia2 Input Module

    Default Data Maps 1734-IA2 Input Module Message Size: 1 Byte Produces (scanner Rx) Consumes (scanner Tx) No consumed data Where:Ch0 = channel 0, Ch1 = channel 1; 0 = off, 1 = on 1734-IA4 Input Module Message Size: 1 Byte Produces (scanner Rx) Consumes (scanner Tx) No consumed data...
  • Page 172: 1734-Oa2 Output Module

    Default Data Maps 1734-OA2 Output Module Message Size: 1 Byte Produces (scanner Rx) No produced data Consumes (scanner Tx) Not used Channel state Where: 0 = off, 1 = on 1734-OA4 Output Module Message Size: 1 Byte Produces (scanner Rx) No produced data Consumes (scanner Tx) Not used...
  • Page 173: 1734-Ob4E, 1734-Ob4 Electronically Protected Output Module

    Default Data Maps 1734-OB4E, 1734-OB4 Electronically Protected Output Module Message Size: 1 Byte Produces (scanner Rx) Not used Channel status (1734-OB4E only) Where: 0 = no error 1 = error Message Size: 1 Byte Consumes (scanner Tx) Not used Channel state Where: 0 = off 1 = on 1734-OB8E, 1734-OB8 Electronically Protected Output Module Message Size: 1 Byte...
  • Page 174: 1734-Ov2E Output Module

    Default Data Maps Message Size: 1 Byte Consumes (scanner Tx) Not used Channel state Where:0 = off, 1 = on 1734-OV2E Output Module Message Size: 1 Byte Produces (scanner Rx) Not used Channel status Where: 0 = no error, 1 = error Message Size: 1 Byte Consumes (scanner Tx) Not used...
  • Page 175: 1734-Ov8E Output Module

    Default Data Maps 1734-OV8E Output Module Message Side: 1 Byte Produces (scanner Rx) Ch2 Ch1 Ch0 Channel status Where: 0 = no error 1 = error Message Size: 1 Byte Consumes (scanner Tx) Ch6 Ch5 Channel state Where: 0 = no error 1 = error 1734-OW2 Relay Sink/Source Output Module Message Size: 1 Byte Consumes (scanner Tx)
  • Page 176: 1734-Ox2 Relay Output Module

    Default Data Maps 1734-OX2 Relay Output Module Message Size: 1 Byte Consumes (scanner Tx) Not used Channel state Where: 0 = NO contact Off, NC contact On 1 = NO contact On, NC contact Off I/O messages are sent to (consumed) and received from (produced) the Analog Module Default POINT I/O modules.
  • Page 177: 1734-Ie2V Analog Voltage Input Module

    Default Data Maps 1734-IE2V Analog Voltage Input Module Message Size: 6 Bytes Produces (scanner Rx) Input Channel 0 - High Byte Input Channel 0 - Low Byte Input Channel 1 - High Byte Input Channel 1 - Low Byte Status Byte for Channel 1 Status Byte for Channel 0 HHA LLA HA CM CF...
  • Page 178: 1734-Oe2V Analog Voltage Output Module

    Default Data Maps 1734-OE2V Analog Voltage Output Module Message Size: 4 bytes 11 10 07 06 05 04 03 02 01 00 Consumes (scanner Tx) Output Channel 0 High Byte Output Channel 0 Low Byte Output Channel 1 High Byte Output Channel 1 Low Byte Message Size: 2 Bytes Produces (scanner Rx)
  • Page 179 Default Data Maps Notes: Publication 1734-UM001D-EN-P - April 2008...
  • Page 180 Default Data Maps Publication 1734-UM001D-EN-P - April 2008...
  • Page 181: Mounting Dimensions

    Appendix Mounting Dimensions Read this appendix for mounting dimensions for the following: About This Appendix • POINT I/O module with a 1734-ADN adapter • POINT I/O module with a 1734-PDN module • POINTBlock modules Publication 1734-UM001D-EN-P - April 2008...
  • Page 182: Point I/O Module With A 1734-Adn, 1734-Acnr, 1734-Aent, Or

    Mounting Dimensions See the figure for mounting dimensions for a POINT I/O module with a POINT I/O Module with a network adapter. The example figure shows a 1734-ADN adapter. 1734-ADN, 1734-ACNR, 1734-AENT, or 1734-APB Adapter Mounting Dimensions L = 2.16 + [# of I/O x 0.47] + [# of EP24DC or FPD x 1.0] in. Allow a 25.4 (1.0) Air Gap All Around L = 54.9 + [# of I/O x 12.0] + [# of EP24DC or FPD x 25.4] mm...
  • Page 183: Point I/O Module With A 1734-Pdn Module

    Mounting Dimensions See the figure for mounting dimensions for POINT I/O module with a POINT I/O Module with a 1734-PDN DeviceNet Communication Interface module. 1734-PDN Module L = 1.0 + [# of I/O x 0.47] + [# of FPD x 1.0] in. Allow a 25.4 (1.0) Air Gap All Around L = 25.4 + [# of I/O x 12.0] + [# of FPD x 25.4] mm...
  • Page 184: Pointblock Module

    Mounting Dimensions See the figure for mounting dimensions for a 1734-D POINTBlock module. POINTBlock Module Gap All Around L = 60.0 + [# of I/O x 12.0] + [# of FPD x 25.4] mm 133.4 (5.25) mm (in) 30977 1734D (HxWxL) 76.2 (3.0) x 60.0 (2.36) x 133.4 (5.25) Secure DIN rail to mounting surface approximately every 200 mm (7.8 in.).
  • Page 185: About This Appendix

    Appendix Configure POINT I/O Modules in RSLogix 5000 Software Read this appendix for information about how to configure digital and analog About This Appendix POINT I/O modules, using RSLogix 5000 software with one of the following: • ControlNet network using a 1734-ACNR adapter •...
  • Page 186 Configure POINT I/O Modules in RSLogix 5000 Software As an example, if you add 1734-OB2E, you see the New Module dialog. 3. Choose Connection at the top of the dialog. 4. Leave the following unchecked: • Inhibit Module • Major Fault On Controller If Connection Fails While in Run Mode 5.
  • Page 187 Configure POINT I/O Modules in RSLogix 5000 Software 6. Choose Module Info to see a dialog that provides identification and status information. 7. See the appropriate sections of this appendix for information about the following tabs and dialogs, which you see based on the module you added: •...
  • Page 188: About Fault/Program Action And Configuration Dialogs

    Configure POINT I/O Modules in RSLogix 5000 Software About Fault/Program Action and Configuration Dialogs You see Fault/Program Action and Configuration dialogs based on the module and connection types. Refer to the following table. For Module Type With Connection Type You See These Tabs Fault/Program Action Configuration Input...
  • Page 189: Understanding Transition To Hard Run Behavior

    Configure POINT I/O Modules in RSLogix 5000 Software The choices for connection type for modules depend on the communication type format for the parent adapter, per the table. Adapter Connection Type Input Output Module Communication Module 1734-OA2 1734-OB2, 1734-OB2E, 1734-OB4E, 1734-OB8E Format 1734-OW2,4 1734-OB4,...
  • Page 190: Working With Dialogs For Digital Input Modules

    Configure POINT I/O Modules in RSLogix 5000 Software When you switch the controller to Hard Run, note the following: • You disable all controls except for the Description field on the General dialog, which remains active in all modes. • You revert to each control that contains an edited value, including the Description field on the General dialog, to include the following dialogs: –...
  • Page 191 Configure POINT I/O Modules in RSLogix 5000 Software See the figure for a Configuration dialog for an 8-point input module. 3. From the Configuration dialog, complete the entries for Input Filter Time (ms) for Off-On and On-Off for each point, referring to the table. Feature Description Channel...
  • Page 192: Working With Dialogs For Digital Output Modules

    Configure POINT I/O Modules in RSLogix 5000 Software Working with Dialogs for Digital Output Modules Read this section to complete the Fault/Program Action and Configuration dialogs for output modules. You typically select these dialogs from the General dialog, when you add an output module with the following entries for connection type: •...
  • Page 193 Configure POINT I/O Modules in RSLogix 5000 Software • with overload and open load diagnostic status. 2. From the Fault/Program Action dialog, complete entries, referring to the table for a summary of how to make these entries. Feature Description Point Displays the channel numbers.
  • Page 194 Configure POINT I/O Modules in RSLogix 5000 Software Enter Values on the Configuration dialog Enter values on this dialog based on the type of module with: • overload diagnostic status. • overload and open load diagnostic status. To complete the entries on this dialog proceed as follows. 1.
  • Page 195 Configure POINT I/O Modules in RSLogix 5000 Software 2. From the Configuration dialog, complete the entries, referring to the table for information about how to complete entries with No Load Detection. Feature Description Point Displays the channel numbers. • Use to determine how a status bit acts after the cause of the Latch Faults fault is removed.
  • Page 196 Configure POINT I/O Modules in RSLogix 5000 Software See the figure where, as an example, if you want to configure all of the channels the same way, you check the No Load Detection header. This checks all the boxes in the column and enables the bit for all the channels in the module.
  • Page 197: Configure Analog Modules

    Configure POINT I/O Modules in RSLogix 5000 Software To configure POINT I/O modules in RSLogix 5000 software, complete these Configure Analog Modules steps. 1. Configure your adapter, referring to the user manual for your adapter for information on how to: •...
  • Page 198: Understanding Data And Connection Formats

    Configure POINT I/O Modules in RSLogix 5000 Software Understanding Data and Connection Formats For analog modules, the choices for data format and connection type are as follows: • Data Format: Integer • Connection Type – Data – Listen only – Listen only - rack optimization –...
  • Page 199: Working With Dialogs For Analog Input Modules

    Configure POINT I/O Modules in RSLogix 5000 Software Working with Dialogs for Analog Input Modules Read this section for information about how to complete entries on the following dialogs for analog input modules: • Configuration • Alarm Configuration • Calibration To display the dialogs, you typically click Configuration, Alarm Configuration, or Calibration at the top of the General dialog.
  • Page 200 Configure POINT I/O Modules in RSLogix 5000 Software 2. From the Configuration dialog, complete entries, referring to the table. For This Value Select Comments • Default for 1734-IE2C analog input module is 16383. High Engineering -32768…32767 • Default for 1734-IE2V analog input module is 10000. •...
  • Page 201 Configure POINT I/O Modules in RSLogix 5000 Software Working with the Alarm Configuration Dialog This dialog does not appear for Listen Only connections. To complete the entries on this dialog, proceed as follows. 1. From the top of the General dialog, click Alarm Configuration. You see an Alarm Configuration dialog for a current or voltage module, based on the type of module you added.
  • Page 202 Configure POINT I/O Modules in RSLogix 5000 Software Alarm Configuration Dialog Default Values Value 1734-IE2C 1734-IE2V High High 16793 9800 High 16547 9500 3113 Low Low 2867 2. From the Alarm Configuration dialog, perform the following: a. Click a channel push button, such as 0 or 1, which is highlighted to show it was pressed, selecting the corresponding channel for the values you enter.
  • Page 203 Configure POINT I/O Modules in RSLogix 5000 Software See the figure for a Calibration dialog for a current input module. 2. Check the Calibrate checkbox to specify which channel to calibrate. 3. Under Calibrate Channels, select One At a Time. 4.
  • Page 204 Configure POINT I/O Modules in RSLogix 5000 Software You see the Low Value dialog. 6. From the Low Value dialog, click Next to start calibration. You see the High Value dialog. 7. From the High Value dialog, click Next to start calibration. You see the Calibration Completed dialog that shows you saved the changed calibration constants of the channel.
  • Page 205: Working With Dialogs For Analog Output Modules

    Configure POINT I/O Modules in RSLogix 5000 Software Working with Dialogs for Analog Output Modules Read this section for information about how to complete entries on the following dialogs for analog output modules: • Configuration • Alarm Configuration • Fault/Program Action •...
  • Page 206 Configure POINT I/O Modules in RSLogix 5000 Software 2. From the Configuration dialog, complete entries, referring to the table. For This Value Select Comments • Default for 1734-OE2C analog output module is 8191. High Engineering -32768…32767 • Default for 1734-OE2V analog output module is 10000. •...
  • Page 207 Configure POINT I/O Modules in RSLogix 5000 Software Working with Alarm Configuration Dialog This dialog does not appear for Listen Only connections. To complete the entries on this dialog, proceed as follows. 1. From the top of the General dialog, click Alarm Configuration. You see an Alarm Configuration dialog for a current or voltage module, based on the type of module you added.
  • Page 208 Configure POINT I/O Modules in RSLogix 5000 Software 5. Check the checkbox for the following, if desired: • Disable All Alarms — A check in the checkbox tells the module to not input alarms. This is disabled in Hard Run only. •...
  • Page 209 Configure POINT I/O Modules in RSLogix 5000 Software 2. From the Fault/Program Action dialog, complete items, referring to the table. For This Value Select Comments • Hold Last State Fault Mode Default is Go to Low Clamp. • Go to Low Clamp •...
  • Page 210 Configure POINT I/O Modules in RSLogix 5000 Software Working with the Calibration Dialog To complete entries on this dialog, proceed as follows. Perform calibration in Hard Run or Remote mode. For information about the tools and steps for calibration, refer to the Calibrating Your Analog Module section of this manual.
  • Page 211 Configure POINT I/O Modules in RSLogix 5000 Software 4. From the Calibration dialog, click Start Calibration, which is active when: • the system is online, and • you selected at least one of the channels. Note that when you press the F1 button on your keyboard or click Help from the wizards and warning messages that appear during calibration you get detailed information about related procedures.
  • Page 212 Configure POINT I/O Modules in RSLogix 5000 Software You see the High Value dialog. 7. From the High Value dialog, follow the instructions you see and click Next to start calibration. 8. If calibration completes successfully, you see the Calibration Completed dialog.
  • Page 213: About This Appendix

    Appendix Configure POINT I/O Modules for DeviceNet Networks Read this appendix to learn how to configure POINT I/O modules in a About This Appendix DeviceNet network. If you are using a ControlNet, EtherNet/IP, or PROFIBUS network, refer to the appropriate manual. •...
  • Page 214: Using The Rsnetworx Commissioning Tool

    Configure POINT I/O Modules for DeviceNet Networks Using the RSNetWorx Commissioning Tool The RSNetWorx commissioning tool lets you commission devices (set the node address and the data rate parameters) that are either connected to a DeviceNet network or connected via a point-to-point connection. The node commissioning tool works through RSLinx software;...
  • Page 215: Use Sequential Auto Addressing

    Configure POINT I/O Modules for DeviceNet Networks Use Sequential Auto Addressing Sequential Auto Addressing (SAA) reassigns the node address of every module to the right of the one you select on the POINTBus network. Each module changes its node address to one greater than its neighbor. Make sure the node address of the selected module is the IMPORTANT desired value before issuing the SAA command.
  • Page 216 Configure POINT I/O Modules for DeviceNet Networks If your network is up, click Browse. 3. After setting up your system, double-click the module you want to configure. If you are online, upload the configuration. A dialog similar to the following appears. 4.
  • Page 217 Configure POINT I/O Modules for DeviceNet Networks Configure Input Modules See the figure for a Device Parameters dialog for a 1734-IB4 input module example. All digital input modules have parameters similar to this example. On this dialog, you see all the parameters for the module. These include filters, autobaud, sequential addressing, and communication rate(if not using autobaud).
  • Page 218 Configure POINT I/O Modules for DeviceNet Networks 2. From the Device Parameters dialog, select Single and change or configure parameters one at a time, or select All to change all selections at once. Note that if autobaud is selected, the communication rate of this module automatically matches the communication rate of the existing devices on the network, and you are prevented from selecting a specific communication rate.
  • Page 219 Configure POINT I/O Modules for DeviceNet Networks 3. From the Device Parameters dialog, select the filter of your choice by selecting and typing in the filter time, noting that each input channel can have its own time selection. 4. From the Device Parameters dialog, click Download to Device. Configure Output Modules To configure output modules, follow this procedure.
  • Page 220 Configure POINT I/O Modules for DeviceNet Networks 2. From the Device Parameters dialog, set parameters for the module to include sequential addressing and autobaud or, if not using autobaud, communication rate. The Groups pull-down menu includes the following: • All parameters •...
  • Page 221 Configure POINT I/O Modules for DeviceNet Networks 3. At the Groups pull-down menu, select Configuration and the parameters you want. 4. Select Single to change or configure parameters one at a time, or All to change all selections at once, noting that configurable parameters include the following: •...
  • Page 222 Configure POINT I/O Modules for DeviceNet Networks See the figures for dialogs for selecting Fault Action and Fault Value. See the figure for a dialog for selecting Idle Action and Idle Value. Publication 1734-UM001D-EN-P - April 2008...
  • Page 223 Configure POINT I/O Modules for DeviceNet Networks See the figure for a dialog for Latching Alarms parameter select. See the figure for a dialog for selecting Enable No Load. Publication 1734-UM001D-EN-P - April 2008...
  • Page 224 Configure POINT I/O Modules for DeviceNet Networks See the figure for a dialog for selecting Reset Mode. See the figure for a dialog for selecting autobaud. 5. From the Device Parameters dialog, click Download to Device. Publication 1734-UM001D-EN-P - April 2008...
  • Page 225 Configure POINT I/O Modules for DeviceNet Networks To configure the 1734-OW2 relay output module, use this procedure. 1. From the General dialog, click Device Parameters to get the dialog for setting parameters. You see the EDS Editor. 2. From the EDS Editor, click Upload to load the latest information. Publication 1734-UM001D-EN-P - April 2008...
  • Page 226 Configure POINT I/O Modules for DeviceNet Networks 3. From the Device Parameters dialog, click Configuration to set the parameters for the module to include sequential addressing and autobaud, or, if not using autobaud, the communication rate. The Groups pull-down menu includes the following: •...
  • Page 227 Configure POINT I/O Modules for DeviceNet Networks Note that configurable parameters include the following: • Fault Action - Fault value/Hold Last State • Fault Value - Off/On • Idle Action - Idle value/Hold Last State • Idle Value - Off/On •...
  • Page 228 Configure POINT I/O Modules for DeviceNet Networks 4. From the Device Parameters dialog, at Groups select All parameters to display each item and POINTBus to display only the run/idle command and autobaud. 5. From the Device Parameters dialog, to monitor the output, click Start Monitor, noting the following: •...
  • Page 229: Configure Analog Modules Using Rsnetworx Software

    Configure POINT I/O Modules for DeviceNet Networks Read this for a description of how to configure any analog module. The Configure Analog Modules 1734-IE2C and 1734-OE2C modules in this procedure are representative of Using RSNetWorx Software input and output analog modules. The actual dialogs for your particular module may not be identical to the ones shown here.
  • Page 230 Configure POINT I/O Modules for DeviceNet Networks 4. From the General dialog, click Device Parameters to see the dialog for setting parameters. An EDS Editor dialog appears. 5. From the EDS Editor dialog, click Upload to upload existing parameters from the device. 6.
  • Page 231 Configure POINT I/O Modules for DeviceNet Networks 8. Change the configuration, or apply the uploaded parameters, noting that to change the parameters you must downlown to the device. To configure the analog output module, use this procedure. 1. Double-click the icon. The General dialog appears.
  • Page 232 Configure POINT I/O Modules for DeviceNet Networks 2. From the General dialog, click Device Parameters to set parameters. You see the EDS Editor dialog. 3. From the EDS Editor dialog, click Upload to upload existing parameters from the device. 4. From the Device Parameters dialog, from Groups select Configuration. Publication 1734-UM001D-EN-P - April 2008...
  • Page 233 Configure POINT I/O Modules for DeviceNet Networks 5. From the Device Parameters dialog, set Run or Idle, noting that any parameter with a lock indicated next to it is nonchangeable.. 6. Select values for current or voltage. For current, click one of the following: •...
  • Page 234 Configure POINT I/O Modules for DeviceNet Networks Note that fault states include the following: • Hold Last state • Go to Low Clamp • Go to High Clamp • Go to Fault Value 7. For Enable Alarm Latch, select Enable Latching Alarms or Disable. 8.
  • Page 235 Configure POINT I/O Modules for DeviceNet Networks 9. For Autobaud, select Enable or Disable. With current or voltage modules if you change range values, note that it affects range or scaling of the module. Publication 1734-UM001D-EN-P - April 2008...
  • Page 236 Notes: Publication 1734-UM001D-EN-P - April 2008...
  • Page 237 Index Numerics default data map 162 troubleshoot 140 1734D-IA16 module wire 26 about 14 1734-IE2C module wire 87 about 16 1734D-IA8XOA8 module default data map 170 about 14 troubleshoot 147 wire 81 wire 55 1734D-IA8XOW8 module 1734-IE2V module about 14 about 16 wire 84 default data map 171...
  • Page 238 Index 1734-OB2EP module wire 38 1734-OW4 module about 13 default data map 167 about 13 troubleshoot 142 default data map 169 wire 37 troubleshoot 144 1734-OB4 module wire 38 1734-OX2 module about 13 default data map 167 about 13 troubleshoot 141 default data map 170 wire 35 troubleshoot 145...
  • Page 239 Index commissioning removable terminal block 24 nodes 211 tool 212 configure analog modules latch alarms 103 using RSLogix 5000 software 195 LED indicators 137 using RSNetWorx software 271 low alarm 108 configure digital modules low low alarm 108 using RSLogix 5000 software 183 using RSNetWorx software 213 configure the module 93 ControlNet network 9...
  • Page 240 Index remove a mounting base 25 RSNetWorx software 206 under range status 105 for DeviceNet node commissioning tool update rate 104 wiring SAA, sequential auto addressing 207 120/220V ac output module 53 scaling 120V ac input modules 49 analog input modules 102 1734-EP24DC module 64 analog output modules 108 1734-FPD module 61...
  • Page 242 Rockwell Automation provides technical information on the Web to assist you in using Rockwell Automation its products. At http://support.rockwellautomation.com, you can find technical Support manuals, a knowledge base of FAQs, technical and application notes, sample code and links to software service packs, and a MySupport feature that you can customize to make the best use of these tools.

Table of Contents