Chapter 5
Configure the IO-Link Master Module
Add the Module to a
Studio 5000 Logix Designer
Application Project
40
Table 9 - Values for Network Address Switches
Value
Description
Exit Protected Mode.
000
Cycle power to the module and restore the switches to their previous values.
For more information, see
Sets the module IP address to 192.168.1.1.
001
This value is valid but not recommended as this IP address is typically used by network switches.
Sets the module IP address to 192.168.1.xxx (where xxx is the value of the network address switches).
002...253
Subnet mask is set to 255.255.255.0 and the gateway address is set to 0.0.0.0.
The module does not have a host name that is assigned to it or uses any Domain Name Server (DNS).
Sets the module IP address to 192.168.1.254.
254
This value is valid but not recommended as this IP address is typically used by network switches.
888
Resets the module to factory default settings.
Enter Protected Mode.
900
Cycle power to the module and restore the switches to their previous values.
For more information, see
The module checks to see if DHCP is enabled.
• If DHCP is enabled, the module requests for an IP address from a DHCP server. The DHCP server
999
also assigns other network address parameters.
• If DHCP is not enabled, the module uses the IP address and other network address parameters
that are stored in nonvolatile memory.

Use the BOOTP/DHCP Tool

The BOOTP/DHCP tool is a standalone server that you can use to set an IP address.
The BOOTP/DHCP tool sets an IP address and other TCP parameters.
You can use the BOOTP/DHCP tool to set the IP address when the device powers up in the out-
of-box state. The out-of-box state assumes that the network address switches on the module
are not set to a valid IP address (see
For instructions on how to use the BOOTP/DHCP tool to set the IP address, see the EtherNet/IP
Network Devices User Manual, publication ENET-UM006.
You must complete the following tasks before you can add the module:
Create a Studio 5000 Logix Designer application project.
Add a controller to the project.
For more information on how to add a controller to a Studio 5000 Logix Designer application
project, see the User Manual for the controller.
After you create a Studio 5000 Logix Designer application project and add a controller to the
project, you can use the following methods to add modules to the project.
Discover Modules
New Module
Rockwell Automation Publication 5032-UM001A-EN-P - April 2023
Protected Mode for IO-Link Master Module on page
Protected Mode for IO-Link Master Module on page
Table
9), and the module is DHCP enabled.
21.
21.