Diagnostic Channels - Rockwell Automation Allen-Bradley ArmorBlock 5000 Series User Manual

8-channel io-link master module
Table of Contents

Advertisement

Table 43 - Structure for AB:Ethernet_Port_Channel:D:0
Name
PortStatus_Pad0
Fault
Uncertain
Connected
FullDuplex
PortStatus_Pad5
PortStatus_Pad6
PortStatus_Pad7
AutonegotiationStatus
Speed
Pad
DisconnectedTimestamp

Diagnostic Channels

The following data types are retrieved as part of the Diagnostic Assembly Instance.
1. Diagnostic Ethernet Channel
- Data Type = AB:Ethernet_Port_Channel:D:0
- Size: 16 bytes
Follow the information in
Data Type
Byte
Valid Values
BOOL
This member acts as padding to ensure byte alignment. It can be renamed.
0 = No fault exists
BOOL
1 = Fault exists
0 = Good data
1 = Uncertain data
If the tag is set to 1, you must troubleshoot the module to correct the cause of the
BOOL
inaccuracy.
IMPORTANT: Once the condition that causes the tag to change to 1 is removed, the tag
automatically resets to 0.
1
0 = Ethernet port is inactive
BOOL
1 = Ethernet port is active
0 = Ethernet port is running in half-duplex mode
BOOL
1 = Ethernet port is running in full-duplex mode
BOOL
This member acts as padding to ensure byte alignment. It can be renamed.
BOOL
This member acts as padding to ensure byte alignment. It can be renamed.
BOOL
This member acts as padding to ensure byte alignment. It can be renamed.
0 = Auto-negotiation in progress.
1 = Auto-negotiation and speed detection failed. Using default values for speed and
duplex. Default values are product-dependent; recommended defaults are 10 Mbps and
half-duplex.
SINT
1
2 = Auto negotiation failed, but detected speed. Duplex was defaulted. Default value is
product-dependent; recommended default is half-duplex mode.
3 = Successfully negotiated speed and duplex mode.
4 = Auto-negotiation not attempted. Forced speed and duplex mode.
• 10 Mbps
INT
2
• 100 Mbps
DINT
4
This member acts as padding to ensure byte alignment. It can be renamed.
LINT
8
The most recent time the port is disconnected.
Rockwell Automation Publication 5032-UM001A-EN-P - April 2023
Appendix D
Table 43
to add each member.
Module Diagnostic Assembly
113

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents