IO-Link Event Log

This section provides information about IO-Link events, event data structure, and a list of
port-level IO-Link events.
Figure 18
shows an example of a port-level IO-Link event log.
To access the port-level IO-Link event log, see
Figure 18 - IO-Link Port Event Log Example
Table 26
describes the enumeration and definition of port-level IO-Link events. For more
information, see the IO-Link Interface and System Specification at io-link.com.
Table 26 - IO-Link Port-Level Event Codes
Event Code ID
Event Type
0x1800
Error
0x1802
Error
0x1803
Error
0x1804
Error
0x1805
Error
0x1806
Error
0x1807
Error
0x1809
Error
0x180A
Error
0x180B
Error
0x180C
Error
0x180D
Error
0x180E
Error
0x180F
Error
0x1810
Error
0x1811
Error
0x1812
Error
0x1813
Error
0x1FF1
Error
0x1FF2
Notification
0x6000
Error
0x6001
Error
0xFF26
Notification
0xFF27
Notification
For IO-Link device event codes, see the IO-Link Interface and System Specification at
io-link.com, and the documentation for the device for more information.
Rockwell Automation Publication 5032-UM001A-EN-P - April 2023
Appendix B
XX - IO-Link on page
Description
No Device (communication)
Incorrect VendorID – Inspection Level mismatch
Incorrect DeviceID – Inspection Level mismatch
Short circuit at C/Q – Check wire connection
PHY overtemperature – Check Master temperature and load
Short circuit at L+ – Check wire connection
Overcurrent at L+ – Check power supply (for example, L1+)
Backup inconsistency – Memory out of range (2048 octets)
Backup inconsistency – Identity fault
Backup inconsistency – Data Storage unspecific error
Backup inconsistency – Upload fault
Parameter inconsistency – Download fault
P24 (Class B) missing or undervoltage
Short circuit at P24 (Class B) – Check wire connection (for example, L2+)
Short circuit at I/Q – Check wiring
Short circuit at C/Q (if digital output) – Check wiring
Overcurrent at I/Q – Check load
Overcurrent at C/Q (if digital output) – Check load
IO-Link PHY communication error
IO-Link port restarted
Invalid cycle time
Revision fault – Incompatible protocol version
Port status changed
Data Storage upload completed
Troubleshoot Your IO-Link Device