Table 31 - IO-Link Master Module Event Input Tags
Name
RunMode
ConnectionFaulted
DiagnosticActive
DiagnosticSequenceCount
Eventxx.Fault
Eventxx.Uncertain
Eventxx.EventDropped
Eventxx.EventRising
Eventxx.EventFalling
Eventxx.CIPSyncValid
Eventxx.CIPSyncTimeout
Eventxx.EventsPending
Eventxx.EventNumber
Eventxx.EventTimestamp
Eventxx.PtxxData

Event Input Tags for IO-Link Master Module

Table 31
describes the available event input tags ('EI').
Data Type
Definition
BOOL
Indicates the operating state of the input.
Indicates if a connection is running.
BOOL
The module sets this tag to 0 when connected. If the
module is not connected, it sets this tag to 1.
Indicates if any diagnostics are active or if the
BOOL
prognostics threshold is reached.
Increments each time that a distinct diagnostic
condition is detected, and each time a distinct
diagnostic condition transitions from detected to not
SINT
detected.
Resets to zero on power cycle. Wraps from 255 (-1) to 1,
skipping zero.
Detects whether the signal is good data. The fault is set
BOOL
to 1 by the originator when the connection is lost.
Indicates that the channel data can be inaccurate but
the degree of inaccuracy is not known.
BOOL
For more information, see
page
17.
Indicates when an event has been discarded
BOOL
because events are occurring faster than they are
being acknowledged.
Indicates whether an event triggered when an input
BOOL
transition results in an event pattern being matched.
Indicates whether an event triggered when an input
BOOL
transition resulted in an event pattern no longer
being matched.
Indicates whether the module is synced with a
BOOL
1588 master.
Indicates that the module was once synced with a 1588
BOOL
master, but is not now due to a timeout.
The number of events currently queued in the modules.
SINT
A value greater than 0 indicates that the controller is not
currently keeping up with the rate of events.
Running count of events, which increments by one each
new time event.
The originator sets EO.Eventxx.EventNumberAck to
DINT
EI.Eventxx.EventNumber to acknowledge receipt of the
event.
When the number of events reaches its maximum value
and rolls over, it rolls over to 1, not 0.
LINT
The time the event occurred.
When set, indicates the corresponding data value
BOOL
(rising or falling depending on configuration) triggered
the event.
Rockwell Automation Publication 5032-UM001A-EN-P - April 2023
Appendix C
IO-Link Master Module and IO-Link Device Tag Definitions
Valid Values
0 = Idle
1 = Run mode
0 = Connection running
1 = Connection not running
0 = No diagnostics active
1 = One or more diagnostics are active or the prognostics
threshold is reached
-128...+127
The value of 0 is skipped except during module powerup.
0 = Good
1 = Bad, causing fault
0 = Good data
1 = Uncertain data
If the tag is set to 1, you must troubleshoot the module to
Fault and Status Reporting on
correct the cause of the inaccuracy.
IMPORTANT: Once the condition that causes the tag to
change to 1 is removed, the tag automatically resets to 0.
0 = An event status has not been dropped
1 = An event status has been dropped
0 or 1
0 or 1
0 = Module not synchronized
1 = Module synchronized
0 = A valid time master has not timed out.
1 = A valid time master was detected on the backplane,
but the time master has timed out. The module is using
its local clock and can be drifting away from the last
known time master.
All positive values
All values
All positive values
0 = Corresponding data value did not trigger the event
1 = Corresponding data value triggered the event
103