Troubleshoot Your Io-Link Master Module; Module Status Indicator; Network Status Indicator - Rockwell Automation Allen-Bradley ArmorBlock 5000 Series User Manual

8-channel io-link master module
Table of Contents

Advertisement

Module Status Indicator

Table 15 - Module Status Indicator
Indicator State
Description
Off
The module is not powered.
Steady green
The module is operating in a normal condition.
Flashing green
The IP address is not set.
Steady red
The module experienced a nonrecoverable fault.
One of the following conditions exists:
• A module firmware update is in progress.
• IP address switches do not match the configuration in use.
Flashing red
• The device has a recoverable fault. See the module diagnostics for more
information.
• The module has powered up and is in the Factory Default state. In this case,
all other indicators flash red and green.
The module is performing a POST (power on self test), which completes within
Flashing red/green
30 seconds.

Network Status Indicator

Table 16 - Network Status Indicator
Indicator State
Description
Off
The module is not configured or does not have an IP address.
Steady green
The module has an IP address and at least one established active connection. None
Flashing green
The module has an IP address, but no active connections are established.
Steady red
There is a duplicate IP address condition or invalid configuration.
Flashing red
One or more connections have timed out.

Troubleshoot Your IO-Link Master Module

This appendix describes how to identify and troubleshoot issues with your ArmorBlock 5000
8-channel IO-Link master module.
Table 15
describes the module status indicator for the ArmorBlock 5000 8-channel IO-Link
master module.
Table 16
describes the network status indicator for the ArmorBlock 5000 8-channel IO-Link
master module.
Rockwell Automation Publication 5032-UM001A-EN-P - April 2023
Recommended Action
Apply power as necessary.
None
Set the IP address using one of the recommended methods. For
more information, see
Configure the IO-Link Master Module on
page
39.
Cycle power to the module. If the fault persists, replace the module.
Complete one of the following:
• Wait for the firmware update to finish.
• Cycle power to the module.
• Use module as necessary.
None
Recommended Action
Configure the module or assign an IP address.
Establish connections as required by the project.
Troubleshoot the issue and remedy the cause.
For example, if a duplicate IP address condition exists, determine
which devices on the network use the same IP address and change
the IP address to unique values.
Use module as necessary.
A
Appendix
79