Rockwell Automation Allen-Bradley ArmorBlock 5000 Series User Manual page 47

8-channel io-link master module
Table of Contents

Advertisement

Available Connection Types
The Connection choice determines what data is exchanged between the owner-controller and
the module.
Table 11
describes the connection types that you can use with the ArmorBlock 5000 8-channel
IO-Link master module.
Table 11 - Connection Types for ArmorBlock 5000 8-channel IO-Link Master Module
Connection Type
Data
Data and Ethernet Status
Data with Events
Data with Events and Ethernet
Status
For more information on how to use the Module Definition parameters for ArmorBlock 5000
8-channel IO-Link master modules, see the Studio 5000 Logix Designer application online Help.
Rockwell Automation Publication 5032-UM001A-EN-P - April 2023
Chapter 5
Description
The module returns the following to the controller:
• General fault data
• Input data
• Counter data
The controller returns the following to the module:
• Output data
The module returns the following to the controller:
• General fault data
• Input data
• Counter data
• Ethernet Status data
The controller returns the following to the module:
• Output data
The module returns the following to the controller:
• General fault data
• Input data
• Counter data
• Event input data
The controller returns the following to the module:
• Output data
• Event output data
The module returns the following to the controller:
• General fault data
• Input data
• Counter data
• Ethernet Status data
• Event input data
The controller returns the following to the module:
• Output data
• Event output data