¡Atención! Antes de manipular el chasis de un equipo o trabajar cerca de una fuente de
alimentación, desenchufar el cable de alimentación en los equipos de corriente alterna
(CA).
Varning! Innan du arbetar med ett chassi eller nära strömförsörjningsenheter skall du för
växelströmsenheter dra ur nätsladden.
DC Power Electrical Safety Guidelines for EX4300
Switches
• A DC-powered device is equipped with a DC terminal block that is rated for the power requirements
of a maximally configured device.
• For permanently connected equipment, a readily accessible disconnect device shall be incorporated
external to the equipment.
• For pluggable equipment, the socket-outlet shall be installed near the equipment and shall be easily
accessible.
• Be sure to connect the ground wire or conduit to a solid central office earth ground.
• A closed loop ring is recommended for terminating the ground conductor at the ground stud.
• Run two wires from the circuit breaker box to a source of 48 VDC.
• A DC-powered device that is equipped with a DC terminal block is intended only for installation in a
restricted-access location.
NOTE: Primary overcurrent protection is provided by the building circuit breaker. This breaker
must protect against excess currents, short circuits, and earth grounding faults in accordance
with NEC ANSI/NFPA 70.
• Ensure that the polarity of the DC input wiring is correct. Under certain conditions, connections with
reversed polarity might trip the primary circuit breaker or damage the equipment.
• The marked input voltage of –48 VDC for a DC-powered device is the nominal voltage associated
with the battery circuit, and any higher voltages are only to be associated with float voltages for the
charging function.