Table 70: Parts Required for Connecting an EX Series Switch to Earth Ground
Switch
Earthing
Terminal
Location
EX6210
Rear panel of
the chassis
(on lower left
side)
EX8208
Left side of
the chassis
Grounding
Grounding Lug
Cable
Specifications
Requirements
The grounding
Panduit LCD2-14A-
cable must be
Q or equivalent
the same gauge
—provided
as the power
feed cables and
as permitted by
the local code.
6 AWG
Panduit LCD2-14A-
(13.3 mm²),
Q or equivalent
minimum 90° C
—provided
wire, or as
permitted by
the local code
(Continued)
Screws and
Additional
Washers
Information
•
Two ¼ -20
x 0.5 in.
screws with
#¼" split-
washer
—provided
•
Two #¼" flat
washers—
provided
•
Two ¼ -20
x 0.5 in.
screws with
#¼" split-
washer
—provided
•
Two #¼" flat
washers—
provided
191