Rack-mounting the components
Page 74 of 488
Lifting system components
553-3041-210
Standard 4.00
Media Gateway. The Media Gateway Expander would be approximately
1/4 in from the Media Gateway.
Note: In the 5u pattern, a "u" is equal to 1.75 in. and includes three holes
spaced at 5/8 in. + 5/8 in. + 1/2 in.
Other data communications equipment can be installed in a rack with
CS 1000E system components.
Ensure that the unit's power cord is appropriate for the area's electrical
service. Do not modify or use the supplied AC power cord if it is not the
correct type.
This chapter contains the following procedures:
•
Procedure 1: "Rack-mounting a CS 1000E Call Server" on
•
Procedure 2: "Removing the cover" on
•
Procedure 3: "Rack-mounting a Media Gateway or Media Gateway
Expander" on
page 80
•
Procedure 4: "Preparing a Signaling Server for rack-mounting" on
page 83
•
Procedure 5: "Rack-mounting a Signaling Server" on
Exercise care when lifting system components. If necessary, get assistance to
lift a component or install components in a rack. Table 11 on page 75 lists the
CS 1000E system components provided by Nortel and the weight of each
September 2007
IMPORTANT!
page 78
page 77
page 86