Bi-directional range

Description
● This function is used to measure both the forward and reverse flow rates based on
flow direction while changing the range.
● Current output changes based on the working range as shown in the diagram on the
right.
● Current is output for either the volume flow rate or mass flow rate set with the analog
output source designation (see section 4.8.1.3).
● Hysteresis can be set in the 0 to 20% working range.
● By setting DO1 or DO2 to "FULL SCALE 2", contact output is activated when "FLOW
RATE FS2" is activated.
Set "ACTIVE ON" or "ACTIVE OFF" separately. (See Section 4.9.5)
● Setting range:
Both VOLUME FLOW FS1 and VOLUME FLOW FS2 are in the ±0.3 to 50 [m/s]
range based on the flow velocity calculated inside the pipe.
Both MASS FLOW FS1 and MASS FLOW FS2 are ±99999999.
* It is necessary to set the piping parameters, as well as the VOLUME FLOW UNIT and MASS FLOW UNIT beforehand.
* If a setting value that exceeds the setting range is entered, "INPUT ERROR" is displayed, and the value returns to the original
setting value.
* If "FLOW RATE UNIT" is changed after setting the range, set the range again.
* If not using FLOW RATE FS2 (if single range), set FLOW RATE FS2 to "0".
<Note> The flow rate unit is the unit selected at "VOLUME FLOW UNIT" and "MASS FLOW UNIT". Specify the "FLOW RATE UNIT"
setting before setting the range. (See section 4.7.2) (See section 4.7.4)
For actual keying, refer to the typical operation indicated below. Set the protection to OFF beforehand. (See Section 4.4.1.)
Operation
Set "BI-DIR" to "RANGE TYPE", 20[m
(example)
Set "RANGE HYS." to 7%.
* Set the PIPE PARAMETER and VOLUME FLOW UNIT beforehand.
Key operation
Press the
ENT
Press the
Press the
Press the
ENT
Press the
ENT
Press the
ENT
Press the
Press the
Press the
ENT
Press the
Press the
Note)
Press the
ENT
――― "VOLUME FLOW FS1" has been registered. ―――
Press the
3
/h] to "VOLUME FLOW FS1", and -10[m
Description
key twice to display "OUTPUT SETUP".
ENT
key once to display "ZERO ADJUSTMENT".
key for 4 times to display "RANGE".
key once to display "RANGE TYPE".
ENT
key once to blink the cursor.
ENT
key twice to display "BI-DIR".
ENT
key once to select "BI-DIR".
key once to display "BI-DIR".
key once to blink the cursor.
ENT
key several times to align the cursor to "5".
key several times to set "2".
To change the decimal point position, align the cursor with a
place to change to, and press the
key once to register.
ENT
key once to display "VOLUME FLOW FS2".
key.
-60-
3
/h] to "VOLUME FLOW FS2".
Display
OUTPUT SETUP
ZERO ADJUSTMENT
SET ZERO
RANGE
RANGE TYPE
RANGE TYPE
RANGE TYPE
RANGE TYPE
VOLUME FLOW FS1
50.0000
VOLUME FLOW FS1
0050.0000
VOLUME FLOW FS1
0050.0000
VOLUME FLOW FS1
0020.0000
VOLUME FLOW FS1
 COMPLETE 
VOLUME FLOW FS1
20.0000
VOLUME FLOW FS2
0.0000
SINGLE
SINGLE
BI-DIR
BI-DIR
m3/h
m3/h
m3/h
m3/h
m3/h
m3/h