Mounting of detector
For sensor spacing, select either method in advance.
● Calculate from flow transmitter
Turn ON the flow transmitter.
Enter the piping information, etc described in Section 4.6.2, and display it.
Display example: PROCESS SETTING S=70mm
When the sensor type is "FSX5" (50 A), "FSX6" (65 A), or "FSX8" (80 A), "S = 70 mm" is displayed. When the sensor type
is "FSXA" (100 A), "S = 90 mm" is displayed.
During wiring work, be sure to turn the power off.
Mounting dimensions diagram
The factory default mounting dimension is 70 mm. When the pipe diameter is 50 A, 65 A, or 80 A, the mounting dimension
does not need to be changed. When the pipe diameter is 100 A, change the mounting dimension to 90 mm.
Mounting dimensions