Range Setting; Damping; Flow Rate Unit Setting; Low-Flow Cutoff Setting - Fuji Electric FSZ Instruction Manual

Integral ultrasonic flowmeter s-flow
Table of Contents

Advertisement

3.9.1. Damping

Description
Used to reduce fluctuation of measured values.
The setting value is a time constant. (Response time of about 63%.)
Setting range: 0 sec, 1 sec, 3 sec, 5 sec, 10 sec, 30 sec, 60 sec, 90 sec
Note) When the damping setting is set to 0 seconds, the response time is as follows.
• System cycle 0.2 sec
• Elapsed time of 0.2 sec or less; Time constant of 0.1 sec
For specific key operations, refer to the example in

3.9.2. Flow rate unit setting

Description
You can set the flow rate unit and total value unit from two different systems of measurement, i.e., the metric and imperial systems.
Metric system (factory default) L
When L is set, the flow rate unit becomes L/min.
When L is set, the total value unit becomes L.
For specific key operations, refer to the example in

3.9.3. Low-flow cutoff setting

Description
Output can be cut off when the flow rate is low.
Enabled for display, analog output (4 to 20 mA), and total value.
Setting range: FSZ08: 0.00 to 99.99 [L/min], (Factory default 0.15 [L/min])
FSZ15: 0.0 to 999.9 [L/min], (Factory default 0.5 [L/min])
FSZ25: 0.0 to 999.9 [L/min], (Factory default 1.5 [L/min])
Note 1) The flowmeter may issue a flow indication when the fluid in the piping is
moving due to convection, even when the valve is closed. Therefore, set the
low-flow cutoff point as necessary.
Note 2) The flow rate unit is the unit selected in "Flow rate unit".
For specific key operations, refer to the example in

3.9.4. Method for correcting measurement value

Description
Used when you want to arbitrarily adjust the measurement value.
Zero point and span adjustments are possible.
Setting range
(1) Zero point: FSZ08: -99.99 to 99.99 [L/min], (Factory default 0.00 [L/min])
FSZ15: -999.9 to 999.9 [L/min], (Factory default 0.0 [L/min])
FSZ25: -999.9 to 999.9 [L/min], (Factory default 0.0 [L/min])
(2) Span:
0.0 to 200.0%
The output value (display value, analog output, and total value output) is calculated using the
following formula.
Measured value × [Span%]
Output =
100
Note 1: The flow rate unit is the unit selected in "Flow rate unit".
For specific key operations, refer to the example in

3.9. Range setting

3.9.7.
3.9.7.
(Refer to
3.9.7.
+ Zero point
(Refer to
3.9.7.
- 24 -
)
3.9.2
)
3.9.2