4.10.2. Setting the Bi-directional range

Description
 The function measures the flow rate of either forward or reverse flow while changing
over the range corresponding to the flow direction.
 The current output changes with the action range as illustrated on the right.
 The hysteresis can be set to between 0 and 20% of the action range.
 Upon setting DO1 and/or DO2 to "FULL SCALE2", a contact outputs "FULL
SCALE2" action.
Select "ACTIVE ON" or "ACTIVE OFF" separately. (See 4.10.5.)
 Settable range: ±0.3 to 10[m/s] in terms of flow velocity in piping for any of FULL
SCALE1 and FULL SCALE2.
* Preset PIPE PARAMETER and FLOW UNIT.
* If a value beyond the settable range is inputted, "INPUT ERROR" appears and
then last setting is resumed.
* If "FLOW UNIT" has been changed after setting the range, redo the range setting.
* When FULL SCALE2 is not used (in the case of single range), set "0" to FULL SCALE2.
<Note> The flow rate unit is as selected by "FLOW UNIT" in "MEASURE SETUP" mode. Before setting range, set the "FLOW UNIT".
(See 4.8.2.)
For actual keying, refer to the typical operation indicated below. Set the protection to OFF beforehand. (See Section 4.4.1.)
Operation
Set "BI-DIR" to "RANGE TYPE", 20[m3/h] to "FULL SCALE1", and -10[m3/h] to "FULL SCALE2".
(example)
Set "RANGE HYS." to 7%.
* Preset "PIPE PARAMETER" and "FLOW UNIT".
Key operation
Press the
Press the
ENT
Press the
Press the
ENT
Press the
Press the
ENT
Press the
Press the
ENT
Press the
Press the
ENT
Press the
Press the
Note) To change the decimal point position, align the cursor with a place
to change to, and press the
Press the
ENT
Press the
- 46 -
Description
key twice to display "OUTPUT SETUP".
key once to display "ZERO ADJUSTMENT".
ENT
key for 4 times to display "RANGE".
key once to display "KIND"
ENT
key once to display "RANGE TYPE"
key twice to blink the cursor.
ENT
key twice, and select "BI-DIR".
key for 4 times to display "RANGE TYPE".
ENT
key once to display "FULL SCALE1".
key once to blink the cursor.
ENT
key several times to align the cursor to "5".
key several times to set "2".
key.
key once to register.
ENT
――― FULL SCALE1 has been registered. ―――
key once to display "FULL SCALE2".
20mA
4mA
Display
OUTPUT SETUP
ZERO ADJUSTMENT
RANGE
KIND
RANGE TYPE
RANGE
RANGE TYPE
RANGE TYPE
FULL SCALE1
50.0000
FULL SCALE1
0050.0000
FULL SCALE1
0050.0000
FULL SCALE1
0020.0000
FULL SCALE1
 COMPLETE 
FULL SCALE1
20.0000
FULL SCALE2
0.0000
Hysteresis
SET ZERO
FLOW RATE
SINGLE
SINGLE
BI-DIR
BI-DIR
m3/h
m3/h
m3/h
m3/h
m3/h
m3/h