Installation - Fuji Electric FSJ Instruction Manual

Ultrasonic flowmeter for steam
Table of Contents

Advertisement

Select an installation location that satisfies the following conditions for ease of maintenance and inspection, service life of
the instrument, and assurance of reliability all considered.
(1) A place where ambient temperature and humidity are -20 to +60°C and 95% RH or less for flow transmitter
(FSJ)
(2) A place not exposed to direct sunshine nor inclement weather.
(3) Space for periodic inspection and wiring work is available.
(4) A place not subjected to radiated heat from a heating furnace, etc.
(5) A place not subjected to corrosive atmosphere.
(6) A place not to be submerged.
(7) A place free from excessive vibration, dust, dirt, and moisture.
(8) A place remote from electrical devices (motor, transformer, etc.) which generate electromagnetic induction
noise, electrostatic noise, etc.
(9) A place not subjected to excessive fluid pulsation such as pump discharge side.
(10) A place that provides enough place for the length of the straight pipe.
(11) A place where drainage is discharged with steam traps and the steam humidity is small.
(12) Avoid places with rapid pressure fluctuation of 0.1 MPaG or above in 10 seconds.

3. INSTALLATION

-8-