Totalization Processing At Error (Burnout) - Fuji Electric FSJ Instruction Manual

Ultrasonic flowmeter for steam
Table of Contents

Advertisement

4.8.2.6. Totalization processing at error (Burnout)

Description
BURNOUT (TOTAL)
● Set integration processing for measurement errors that may occur due to such reasons as splash contamination in the fluid. (same for
both total display, total pulse output)
● Settable range:
HOLD
: Stops the total (as factory set).
NOT USED : Continues the total according to the measured value marked immediately before the error occurrence.
BURNOUT TIMER
● Sets the time from error occurrence to error processing.
● Settable range: 10 to 900sec (factory set: 10sec) Please set 10 seconds or more.
The total continues until the burnout timer is activated.
For actual keying, refer to the typical operation indicated below. Set the protection to OFF beforehand. (See Section 4.4.1.)
Operation
Change the processing from "BURNOUT" to "HOLD", and change the burnout timer setting from 10 seconds to 15
(example)
seconds.
Key operation
Press the
Press the
ENT
Press the
Press the
ENT
Press the
Because HOLD (factory set) is already registered, go to the next step.
Note) For setting "NOT USED", press the
to select "NOT USED".
Press the
Press the
ENT
Press the
Press the
Press the
ENT
――― "BURNOUT TIMER" has been registered. ―――
Press the
ESC
enter the measurement mode.
Description
key twice to display "OUTPUT SETUP".
key once to display "ZERO ADJUSTMENT".
ENT
key for 6 times to display "TOTAL".
key once to display "TOTAL MODE".
ENT
key for 6 times to display "BURNOUT(TOTAL)".
ENT
key once to display "BURNOUT TIMER".
key once to blink the cursor.
ENT
key twice to move the cursor.
key for 5 times to display "5".
key once to register.
ENT
key twice and then press the
ESC
key, and the
key
key for 3 times to
-52-
Display
OUTPUT SETUP
ZERO ADJUSTMENT
TOTAL
TOTAL MODE
BURNOUT(TOTAL)
BURNOUT TIMER
BURNOUT TIMER
BURNOUT TIMER
BURNOUT TIMER
BURNOUT TIMER
 COMPLETE 
BURNOUT TIMER
0.000
m/s
0.000
m3/h
CLEAR
START
HOLD
10sec
0
10sec
0
01
sec
5
01
sec
15sec