Bi-Directional Auto 2 Range - Fuji Electric FSJ Instruction Manual

Ultrasonic flowmeter for steam
Table of Contents

Advertisement

Bi-directional auto 2 range

Description
● This function is used to measure both the forward and
reverse flow rates based on flow rate and flow
direction while changing the range.
● Current output changes based on the working range
as shown in the diagram on the right.
● Current is output for either the volume flow rate or
mass flow rate set with the analog output source
designation (see section 4.8.1.3).
● Hysteresis can be set in the 0 to 20% range for the
smaller of the span for full scale 1 and full scale 2, or
full scale 3 and full scale 4.
● By setting DO1 or DO2 to "FULL SCALE 2", contact
output is activated when "FLOW RATE FS2" is
activated.
Set "ACTIVE ON" or "ACTIVE OFF" separately. (See Section 4.9.5)
● Setting range:
Both VOLUME FLOW FS1 and VOLUME FLOW FS2 are in the ±0.3 to 50 [m/s] range based on the flow velocity calculated inside the
pipe.
Both MASS FLOW FS1 and MASS FLOW FS2 are ±99999999.
By setting FLOW FS1 and FLOW FS2, FLOW FS3 and FLOW FS4 are set automatically.
The relationship between FLOW FS1 and FLOW FS3, and FLOW FS2 and FLOW FS4 is shown below.
|FULL SCALE 1|=|FULL SCALE 3|
|FULL SCALE 2|=|FULL SCALE 4|
* It is necessary to set the piping parameters, as well as the VOLUME FLOW UNIT and MASS FLOW UNIT beforehand.
* If a setting value that exceeds the setting range is entered, "INPUT ERROR" is displayed, and the value returns to the original
setting value.
* If "FLOW RATE UNIT" is changed after setting the range, set the range again.
* If not using FLOW RATE FS2 (if single range), set FLOW RATE FS2 to "0".
(Note 1) The flow rate unit is the unit selected at "VOLUME FLOW UNIT" and "MASS FLOW UNIT". Specify the "FLOW RATE UNIT"
setting before setting the range. (See section 4.7.2) (See section 4.7.4)
For actual keying, refer to the typical operation indicated below. Set the protection to OFF beforehand. (See Section 4.4.1.)
Operation
Set "BI-DIR AUTO 2" to "RANGE TYPE", 10[m
(example)
FS2".
Set "RANGE HYS." to 7%.
* Set the PIPE PARAMETER and VOLUME FLOW UNIT beforehand.
Key operation
Press the
Press the
ENT
Press the
Press the
ENT
Press the
ENT
Press the
Press the
ENT
Press the
Press the
ENT
Press the
Press the
Note) To change the decimal point position, align the cursor with a place
to change to, and press the
Description
key twice to display "OUTPUT SETUP".
key once to display "ZERO ADJUSTMENT".
ENT
key for 4 times to display "RANGE".
key once to display "RANGE TYPE".
ENT
key once to blink the cursor.
ENT
key for 3 times to display "BI-DIR AUTO 2".
key once to select "BI-DIR AUTO 2".
ENT
key twice to display "VOLUME FLOW FS1".
key once to blink the cursor on the 2nd line.
ENT
key several times to align the cursor to "2".
key several times to change to "1".
key.
/h] to "VOLUME FLOW FS1", and 60[m
3
-62-
/h] to "VOLUME FLOW
3
Display
OUTPUT SETUP
ZERO ADJUSTMENT
RANGE
RANGE TYPE
RANGE TYPE
RANGE TYPE
BI-DIR AUTO 2
RANGE TYPE
BI-DIR AUTO 2
VOLUME FLOW FS1
20.0000
VOLUME FLOW FS1
0020.0000
VOLUME FLOW FS1
0020.0000
VOLUME FLOW FS1
0010.0000
CLEAR
SINGLE
SINGLE
m3/h
m3/h
m3/h
m3/h