S3: Secondary Pi (Pi2) Control - YASKAWA iQpump1000 Quick Start Manual

Ac drive
Hide thumbs Also See for iQpump1000:
Table of Contents

Advertisement

B.13 S: Special Application
No.
(Addr.
Name
Hex)
S2-15
Sequence Timer 3
(3214)
Reference Source
S2-16
Sequence Timer 4 Start
(3215)
Time
S2-17
Sequence Timer 4 Stop
(3216)
Time
S2-18
Sequence Timer 4 Day
(3217)
Selection
S2-19
Sequence Timer 4
(3218)
Selection
S2-20
Sequence Timer 4
(3219)
Reference Source
<1> Setting the sequence timer start time to a higher value than the sequence timer stop time disables that sequence timer.
u

S3: Secondary PI (PI2) Control

No.
(Addr.
Name
Hex)
S3-01
(321A) Secondary PI Enable
Selection
S3-02
(321B) Secondary PI User
Display
322
LCD Display
Selects the frequency reference source used for running the
Tmr 3 Ref Source
drive when sequence timer 3 is active (only applicable when
0: Operator (d1-01)
S2-14 is set to 1 or 2).
1: Operator (d1-02)
0: Operator (d1-01)
2: Operator (d1-03)
1: Operator (d1-02)
3: Operator (d1-04)
2: Operator (d1-03)
4: Terminals
3: Operator (d1-04)
5: Serial com
4: Terminals
6: Option PCB
5: Serial communication
7: Pulse Input
6: Option card
8: Set by b1-01
7: Pulse input
8: Set by b1-01
Sets the start time for timer 4. The value must be set less than
or equal to S2-17.
Tmr 4 Start Time
Sets the stop time for timer 4. The value must be set greater than
or equal to S2-16.
Tmr 4 Stop Time
Tmr 4 Day Sel
Sets the days for which sequence timer 4 is active.
0: Timer disabled
0: Timer disabled
1: Daily
1: Daily
2: Mon - Fri
2: Mon - Fri
3: Sat - Sun
3: Sat - Sun
4: Monday
4: Monday
5: Tuesday
5: Tuesday
6: Wednesday
6: Wednesday
7: Thursday
7: Thursday
8: Friday
8: Friday
9: Saturday
9: Saturday
10: Sunday
10: Sunday
Tmr 4 Seq Sel
Sets the action that occurs when sequence timer 4 is active.
0: Digital out only
0: Digital output only
1: Run
1: Run
2: Run - PI Disable
2: Run - PI disable
Selects the frequency reference source used for running the
Tmr 4 Ref Source
drive when sequence timer 4 is active (only applicable when
0: Operator (d1-01)
S2-19 is set to 1 or 2).
1: Operator (d1-02)
0: Operator (d1-01)
2: Operator (d1-03)
1: Operator (d1-02)
3: Operator (d1-04)
2: Operator (d1-03)
4: Terminals
3: Operator (d1-04)
5: Serial com
4: Terminals
6: Option PCB
5: Serial communication
7: Pulse Input
6: Option card
8: Set by b1-01
7: Pulse input
8: Set by b1-01
LCD Display
Determines when the secondary PI controller is enabled.
0: Disabled
PI2 Enable Sel
1: Always
0: Disabled
2: Drive running
1: Always
3: Motor running
2: Drive running
3: Motor running
Note:
Sets the scale value of 100% PI input.
PI2 UsrDspMaxVal
Description
Description
Setting 3 does not run the motor at zero speed,
baseblock, or in DC injection.
YASKAWA TOEP YAIP1W 01A YASKAWA AC Drive - iQpump1000 Quick Start Guide
Values
Page
Default: 8
Range: 0 to 8
Default: 00:00
Min.: 00:00
<1>
Max.: 24:00
Default: 00:00
Min.: 00:00
<1>
Max.: 24:00
Default: 0
Range: 0 to 10
Default: 0
Range: 0 to 2
Default: 8
Range: 0 to 8
Values
Page
Default: 0
Range: 0 to 3
Default: 10000
Min.: 0
Max.: 60000