Max Geothrm Speed
Frequency
Reference (Hz)
Min Geothrm Speed
The drive can also be programmed for inverse operation by changing the parameter settings in Q2-03 to Q2-08 as
shown in
Figure
4.9.
Max Geothrm Speed
Frequency
Reference (Hz)
Min Geothrm Speed
8.
Set the response to temperature feedback signal loss. The drive will monitor the feedback signal for signal loss. This
function can be disabled by setting Q2-09 to 0. When a wire break is detected (or if no analog input is programmed
for Geothermal Temp), a "TLGI - Geothermal Input" fault or "Temp Lost – Geothermal Input" alarm will be triggered
depending on the setting of Q2-09. If Q2-09 is set to 2 (fault), the drive will only fault when running in AUTO Mode. It
will only display the alarm if not running or if it is running in HAND Mode.
9.
Set the Geothermal Sleep characteristics. The drive will sleep if the drive runs at the minimum speed (Q2-03) for the
time set in Q2-10. Setting Q2-11 to 0 disables the sleep function (default setting).
10.
Set the wake up characteristics. The drive will wake from Geothermal Sleep when Geothermal Temperature (U1-80)
is greater than the "High Temp @ Min" plus the Geothermal Wake Level (Q2-07 + Q2-11) or is less than "Low Temp
@ Min" minus the Geothermal Wake Level (Q2-06 – Q2-11) for more than the Geothermal Wake Delay Time (Q2-12).
11.
The default settings will allow the drive to automatically restart after power loss if the drive was running at the time of
power loss. Set P4-10 to 1 to disable this function.
12.
Press the AUTO key to start the drive with PI control (water depth control). Press the OFF key to stop the drive.
13.
The pump can be run in HAND (LOCAL) Mode for maintenance purposes by pressing the HAND key while the drive
is stopped. The HAND key acts as a start button. Press the OFF button to stop the drive. Press AUTO to return the
drive to geothermal control. The HAND speed reference can be set in P5-02 (Hand Reference 1). Disable the HAND
key by setting P5-04 to 0 (disabled).
YASKAWA TOEP YAIP1W 01A YASKAWA AC Drive - iQpump1000 Quick Start Guide
(Q2-04)
(Q2-03)
Low Temp
@ Max
(Q2-05)
Figure 4.8 Normal Temperature Regulation
(Q2-04)
(Q2-03)
Low Temp
@ Max
(Q2-05)
Figure 4.9 Inverse Temperature Regulation
4.5 iQpump Presets and Functions
Low Temp
High Temp
@ Min
@ Min
(Q2-06)
(Q2-07)
Temperature ( ºF )
Low Temp
High Temp
@ Min
@ Min
(Q2-06)
(Q2-07)
Temperature ( ºF )
High Temp
@ Max
(Q2-08)
High Temp
@ Max
(Q2-08)
4
123