5.5 Auto-Tuning Fault Detection
HOA Keypad Display
End7
Cause
The entered no-load current value was outside the
allowable range.
Auto-Tuning results were less than 5% of the
motor rated current.
HOA Keypad Display
Er-01
Cause
Motor data or data entered during Auto-Tuning
was incorrect
.
Motor output power and motor-rated current
settings (T1-02 and T1-04) do not match.
Motor rated current and detected no-load current
are inconsistent.
HOA Keypad Display
Er-02
Cause
An alarm was triggered during Auto-Tuning.
HOA Keypad Display
Er-03
Cause
Auto-Tuning canceled by pressing STOP button. Auto-Tuning did not complete properly. Restart Auto-Tuning.
HOA Keypad Display
Er-04
Cause
Motor data entered during Auto-Tuning was
incorrect.
Results from Auto-Tuning are outside the
parameter setting range or the tuning process took
too long.
Faulty motor cable or cable connection.
HOA Keypad Display
Er-05
Cause
Motor data entered during Auto-Tuning was
incorrect.
Results from Auto-Tuning are outside the
parameter setting range or the tuning process took
too long.
The load was too high during Rotational Auto-
tuning.
208
No-Load Current Alarm
Check and correct faulty motor wiring.
Double-check the data entered for the Auto-Tuning process.
Motor Data Error
• Check that the motor data entered to T1 parameters matches motor nameplate input before Auto-
Tuning.
• Restart Auto-Tuning and enter the correct information.
• Check the drive and motor capacities.
• Correct the settings of parameters T1-02 and T1-04.
• Check the motor rated current and no-load current.
• Correct the settings of parameters T1-04 and E2-03.
Minor Fault
Exit the Auto-Tuning menu, check the alarm code, remove the alarm cause, and repeat Auto-Tuning.
STOP Button Input
Line-to-Line Resistance Error
• Make sure the data entered to the T1 parameters match the information written on the motor
nameplate.
• Restart Auto-Tuning and enter the correct information.
Check and correct faulty motor wiring.
No-Load Current Error
• Make sure the data entered to the T1 parameters match the information written on the motor
nameplate.
• Restart Auto-Tuning and enter the correct information.
• Check and correct faulty motor wiring.
• Perform Rotational Auto-Tuning.
• Disconnect the motor from machine and restart Auto-Tuning. If motor and load cannot be
uncoupled make sure the load is lower than 30%.
• If a mechanical brake is installed, make sure it is fully lifted during tuning.
YASKAWA TOEP YAIP1W 01A YASKAWA AC Drive - iQpump1000 Quick Start Guide
Error Name
Possible Solutions
Error Name
Possible Solutions
Error Name
Possible Solutions
Error Name
Possible Solutions
Error Name
Possible Solutions
Error Name
Possible Solutions

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents