B.12 Q: PID Controller Parameters
No.
(Addr.
Name
Hex)
Q4-08
(0EF5) Level Control Minimum
Speed
Q4-09
(0EF6) Low Level Detection
Level
Q4-10
(0EF7) Low Level Detection
Time Delay
Q4-11
Low Level Behavior
(0EF8)
Q4-12
(0EF9) Water Level Control
Auto-Restart Time
Q4-13
(0EFA) Level Control
Proportional Gain
Q4-14
(0EFB) Level Control Integral
Time
Q4-15
Low Water Level
(0EFC)
Detection Time Unit
Water Level Analog
Q4-16
Input Wire-Break
(0EFD)
Detection
<1> Units are determined by Q4-15, Low Water Level Detection Time Unit, setting.
u

Q5: Suction Pressure Control

No.
(Addr.
Name
Hex)
Q5-01
Suction Pressure Select
(0F20)
Q5-02
Suction Transducer
(0F21)
Scaling
Q5-03
Suction Pressure
(0F22)
Setpoint
Q5-04
Minimum Suction
(0F23)
Pressure
318
LCD Display
Sets the minimum speed at which the drive will run when the
drive is controlling the water level.
Level Min Spd
When the drive is controlling pressure or if this parameter is set
less than P1-06 and P4-12, parameters P1-06 and P4-12 will be
used as the minimum speed.
Sets the level below which the water level must drop for the time
set in Q4-10 to trigger the drive response set in Q4-11.
Low Level Detect
Setting this parameter to 0.0 will disable the function.
Sets the length of time that the water level must fall below the
level set in Q4-09 to trigger the drive response set in Q4-11.
Low Lvl Det Tm
Selects drive response when the water level drops below the
Low Lvl Behavior
level set in Q4-09 for the time set in Q4-10.
0: No Display
0: No display (digital output only)
1: Alarm Only
1: Alarm only
2: Fault
2: Fault
3: Restart (Q4-12)
3: Restart (time set by Q4-12)
Sets the length of time that the drive will wait before attempting
an auto-restart of the Low Water Level fault.
WtrLvl Restart
This parameter is effective only when Q4-11 is set to 3 and
L5-01 is set to a value greater than 0.
Sets the proportional gain for the water level control.
Lvl Ctrl P Gain
Sets the integral time for the water level control.
Setting this parameter to 0.0 disables the water level control
Lvl Ctrl I Time
integrator.
Determines the time unit for Q4-10, Low Level Detection Time
Low Lvl Det Unit
Delay.
0: Minutes (min)
0: Minutes (min)
1: Seconds (sec)
1: Seconds (sec)
Sets the behavior when the analog input selected for water level
WL Wire Break
feedback is programmed to receive a 4-20 mA signal and the
0: No Display
signal is lost.
1: Alarm Only
0: No display
2: Fault
1: Alarm only
2: Fault (no retry, coast to stop)
LCD Display
Sets the method of operation for the Suction Control / Vacuum
Suction Pres Sel
Control function.
0: Disabled
0: Disabled
1: Suction Pressure
1: Suction pressure (PSI)
2: Vacuum ("Hg)
2: Vacuum ("Hg)
Sets the full scale (20 mA) output of the pressure transducer that
Suction Scaling
is connected to the analog input terminal programmed for
"WaterLvl/Suction" (H3-0o = 23).
Sets the amount of suction pressure to which the drive will
attempt to regulate.
Suction Setpoint
Sets the level below which the suction pressure must fall for
longer than the Q5-05 time to put the drive to sleep and turn off
Min Suction Pres
all lag pumps.
Description
Description
YASKAWA TOEP YAIP1W 01A YASKAWA AC Drive - iQpump1000 Quick Start Guide
Values
Page
Default: 0.00 Hz
Min.: 0.00
Max.: 400.00
Default: 0.0 ft
Min.: 0.0
Max.: 1200.0
<1>
Default: 0.0
Min.: 0.0
Max.: 300.0
Default: 1
Range: 0 to 3
Default: 5.0 min
Min.: 0.1
Max.: 6000.0
Default: 2.00
Min.: 0.00
Max.: 25.00
Default: 5.0 s
Min.: 0.0
Max.: 360.0
Default: 0
Range: 0, 1
Default: 2
Range: 0 to 2
Values
Page
Default: 0
Range: 0 to 2
Default: 100.0
<1>
Min.: 5.0
Max.: 1200.0
<1>
Default: 20.0
169
Min.: 0.0
Max.: 1200.0
<1>
Default: 10.0
Min.: 0.0
Max.: 1200.0