3.6 Main Circuit Wiring
Drive Model
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
–, +1, +2
2A0030
B1, B2
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
–, +1, +2
2A0040
B1, B2
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
–, +1, +2
2A0056
B1, B2
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
–, +1, +2
2A0069
B1, B2
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
–, +1, +2
2A0081
B1, B2
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
<2>
–, +1
2A0110
B1, B2
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
–, +1
<2>
2A0138
B1, B2
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
<2>
–, +1
2A0169
+3
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
<2>
–, +1
2A0211
+3
88
Recomm. Gauge
Terminal
AWG, kcmil
Wire Range
AWG, kcmil
8
10 to 6
8
10 to 6
10 to 6
14 to 10
<1>
10 to 8
8
6
8 to 6
8
8 to 6
12 to 10
<1>
10 to 8
8
4
6 to 4
4
6 to 4
6 to 4
10 to 6
6
8 to 6
3
4 to 3
3
4 to 3
4 to 3
8 to 6
6
6 to 4
2
3 to 2
2
3 to 2
3 to 2
6
6 to 4
1/0
3 to 1/0
1/0
3 to 1/0
2 to 1/0
6 to 1/0
6
6 to 4
2/0
1 to 2/0
2/0
1 to 2/0
1/0 to 3/0
4 to 2/0
4
4/0
2/0 to 4/0
4/0
3/0 to 4/0
1 to 4/0
1/0 to 4/0
4
4 to 2
1/0 × 2P
1/0 to 2/0
1/0 × 2P
1/0 to 2/0
1 to 4/0
1/0 to 4/0
4
4 to 1/0
YASKAWA TOEP YAIP1W 01A YASKAWA AC Drive - iQpump1000 Quick Start Guide
Screw
Size
M4
M5
M4
6
M5
M6
M5
M6
M8
M5
M6
M8
6
M5
M6
M8
M10
4
M8
M10
M10
Tightening Torque
N·m (lb.in.)
2.1 to 2.3
(18.4 to 20.4)
2 to 2.5
(17.7 to 22.1)
2.1 to 2.3
(18.4 to 20.4)
2 to 2.5
(17.7 to 22.1)
5.4 to 6.0
(47.8 to 53.1)
2.7 to 3.0
(23.9 to 26.6)
4 to 6
(35.4 to 53.1)
9.9 to 11.0
(87.6 to 97.4)
2.7 to 3.0
(23.9 to 26.6)
4 to 6
(35.4 to 53.1)
9.9 to 11.0
(87.6 to 97.4)
2.7 to 3.0
(23.9 to 26.6)
4 to 6
(35.4 to 53.1)
9 to 11
(79.7 to 97.4)
18 to 23
(159 to 204)
9 to 11
(79.7 to 97.4)
18 to 23
(159 to 204)
18 to 23
(159 to 204)

Hide quick links: