b5-38, b5-39: PID Setpoint User Display, PID Setpoint Display Digits
When parameter b5-20 is set to 3, parameters b5-38 and b5-39 set a user-defined display for the PID setpoint (b5-19) and PID
feedback monitors (U5-01, U5-04).
Parameter b5-38 determines the display value when the maximum frequency is output and parameter b5-39 determines the
number of digits. The setting value is equal to the number of decimal places.
No.
b5-38
b5-39
n
C1-01 to C1-04: Accel, Decel Times 1 and 2
Two different sets of acceleration and deceleration times can be set in the drive by digital inputs, motor selection, or switched
automatically.
Acceleration time parameters always set the time to accelerate from 0 Hz to the maximum output frequency (E1-04).
Deceleration time parameters always set the time to decelerate from maximum output frequency to 0 Hz. C1-01 and C1-02
are the default active accel/decel settings.
No.
C1-01
C1-02
C1-03
C1-04
<1> The setting range for the acceleration and deceleration times is determined by the accel/decel time setting units in C1-10. For example, if the time
is set in units of 0.01 s (C1-10 = 0), the setting range becomes 0.00 to 600.00 s.
Switching Acceleration Times by Digital Input
Accel/decel time 1 is active by default if no input is set. Activate accel/decel times 2, 3, and 4 by digital inputs
(H1-oo = 7 and 1A) as explained in
Accel/Decel Time Sel. 1
H1-oo = 7
0
1
Figure 4.33
shows an operation example for changing accel/decel. times. The example below requires that the stopping method
be set for "Ramp to stop" (b1-03 = 0).
n
E2-01: Motor Rated Current
Provides motor control, protects the motor, and calculates torque limits. Set E2-01 to the full load amps (FLA) stamped on
the motor nameplate. If Auto-Tuning completes successfully, the value entered to T1-04 will automatically be saved to E2-01.
YASKAWA TOEP YAIP1W 01A YASKAWA AC Drive - iQpump1000 Quick Start Guide
4.6 Basic iQpump Setup and Application Preset Parameters
Name
PID Setpoint User Display
PID Setpoint Display Digits
Parameter Name
Acceleration Time 1
Deceleration Time 1
Acceleration Time 2
Deceleration Time 2
Table
4.19.
Table 4.19 Accel/Decel Time Selection by Digital Input
Accel/Decel Time Sel. 2
H1-oo = 1A
0
0
Decel Time 1
(C1-02)
Accel Time 1
(C1-01)
Output
frequency
ON
FWD (REV)
Run command
Accel/Decel Time Selection 1
(Terminals S1 to S8, H1- oo = "7")
Figure 4.33 Timing Diagram of Accel/Decel Time Change
Setting Range
1 to 60000
Setting Range
0.0 to 6000.0 s
Acceleration
C1-01
C1-03
Decel Time 2
(C1-04)
Accel Time 2
(C1-03)
Decel Time 1
(C1-02)
Time
OFF
ON
ON
OFF
Default
Determined by
b5-20
Determined by
0 to 3
b5-20
Default
20.0 s
<1>
10.0 s
Active Times
Deceleration
C1-02
C1-04
4
157