Drive fails to operate properly due to noise
interference
Overexcitation gain is set too high
Run command was applied while motor
was coasting
The rated output current of the drive is too
small
HOA Keypad Display
oFA00
Cause
The option card installed into port CN5-A
is incompatible with the drive
HOA Keypad Display
oFA01
Cause
The option card connection to port CN5-A
is faulty
HOA Keypad Display
oFA03 to oFA06
oFA10, oFA11
oFA12 to oFA17
oFA30 to oFA43
Cause
Option card or hardware is damaged
HOA Keypad Display
oFb00
Cause
The option card installed into port CN5-B
is incompatible with the drive
A communication option card has been
installed in option port CN5-B
HOA Keypad Display
oFb01
Cause
The option card connection to port CN5-B
is faulty
YASKAWA TOEP YAIP1W 01A YASKAWA AC Drive - iQpump1000 Quick Start Guide
• Review the possible solutions provided for handling noise interference.
• Review the section on handling noise interference and check the control circuit lines, main circuit lines,
and ground wiring.
• Check if the fault occurs simultaneously with overexcitation function operation.
• Consider motor flux saturation and reduce the value of n3-13 (Overexcitation Deceleration Gain).
• Set b3-01 to 1 to enable Speed Search at Start.
• Program the Speed Search command input through one of the multi-function contact input terminals
(H1-oo = 61 or 62).
Use a larger drive.
Option Card Connection Error at Option Port CN5-A
Option compatibility error
Check if the drive supports the option card to be installed. Contact Yaskawa for assistance.
Option Card Fault at Option Port CN5-A
Option not properly connected
• Turn off the power and reconnect the option card.
• Check if the option card is properly plugged into the option port. Make sure the card is fixed properly.
• If the option is not a communication option card, try to use the card in a different option port. If the option
card works properly in a different option port, CN5-A is damaged, and the drive requires replacement. If
the error persists (oFb01 or oFC01 occur), replace the option card.
Option Card Error Occurred at Option Port CN5-A
Option Card Connection Error (CN5-A)
Communication Option Card Connection Error (CN5-A)
• Cycle power to the drive.
• If the problem continues, replace the control board or the entire drive. Contact Yaskawa or a Yaskawa
representative for instructions on replacing the control board.
Option Card Fault at Option Port CN5-B
Option compatibility error
Make sure the drive supports the option card to be installed. Contact Yaskawa for assistance.
Communication option cards are only supported by option port CN5-A. It is not possible to install more than
one communication option.
Option Card Fault at Option Port CN5-B
Option not properly connected
• Turn off the power and reconnect the option card.
• Check if the option card is properly plugged into the option port. Make sure the card is fixed properly.
• Try to use the card in a different option port. If the option card works properly in a different option port,
CN5-B is damaged, and the drive requires replacement. If the error persists (oFA01 or oFC01 occur),
replace the option card.
Fault Name
Possible Solution
Fault Name
Possible Solution
Fault Name
Possible Solution
Fault Name
Possible Solution
Fault Name
Possible Solution