4.6 Basic iQpump Setup and Application Preset Parameters
10 V
Output Voltage
3 V
0 V
0%
n
H4-07, H4-08: Multi-Function Analog Output Terminal FM, AM Signal Level Selection
Sets the voltage output level of U parameter (monitor parameter) data to terminal FM and terminal AM using parameters
H4-07 and H4-08.
No.
H4-07
H4-08
Setting 0: 0 to 10 V
Setting 1: -10 V to 10 V
Setting 2: 4 to 20 mA
n
L5-01: Number of Auto Restart Attempts
Sets the number of times that the drive may attempt to restart itself.
When the counter reaches the number set to L5-01, the operation stops and the fault must be manually cleared and reset.
The restart counter is incremented at each restart attempt, regardless of whether the attempt was successful. When the counter
reaches the number set to L5-01, the operation stops and the fault must be manually cleared and reset.
The number of fault restarts is reset to zero when:
• The drive operates normally for 10 minutes following a fault restart.
• A fault is cleared manually after protective functions are triggered.
• The power supply is cycled.
No.
L5-01
n
L5-04: Fault Reset Interval Time
Determines the amount of time to wait between restart attempts when parameter L5-05 is set to 1.
No.
L5-04
n
o1-08: Third Line User Monitor Selection
Selects the monitor that is shown in the third line. Effective only when o1-06 is set to 1.
Enter the last three digits of the monitor parameter number to be displayed: Uo-oo. For example, set "403" to display
monitor parameter U4-03.
No.
o1-07
n
P1-01: Pump Mode
Selects the base operation mode of the drive controller.
164
H4-07, 08 = 0
Bias 30%
Gain 100%
Bias 0%
Gain 100%
100%
Monitor Value
Figure 4.37 Analog Output Gain and Bias Setting Example 3
Name
Multi-Function Analog Output Terminal FM
Signal Level Selection
Multi-Function Analog Output Terminal AM
Signal Level Selection
Name
Number of Auto Restart Attempts
Name
Fault Reset Interval Time
Name
Second Line User Monitor Selection
H4-07, 08 = 1
10V
Output Voltage
3 V
-100%
Setting Range
Setting Range
Setting Range
Setting Range
YASKAWA TOEP YAIP1W 01A YASKAWA AC Drive - iQpump1000 Quick Start Guide
Gain = 100%
Bias = 30%
Gain = 100%
Bias = 0%
100%
Monitor Value
-4 V
-10 V
0 to 2
0 to 2
0 to 10 Times
0.5 to 600.0 s
101 to 799
Default
0
0
Default
5 Times
Default
10.0 s
Default
103