B.7 H Parameters: Multi-Function Terminals
H1-oo
Function
Setting
1B
Program lockout
1E
Reference sample hold Ref Sample Hold
20 to 2F External pump fault
30
PID integral reset
31
PID integral hold
Multi-Step Speed
32
Reference 4
34
PID soft starter cancel
35
PID input level selection PID Input Invert
Forward run command
40
(2-Wire sequence)
Reverse run command
41
(2-Wire sequence)
Run command
42
(2-Wire sequence 2)
FWD/REV command
43
(2-Wire sequence 2)
47
Node setup
51
Sequence Timer Disable SeqTimer Disable
278
H1 Multi-Function Digital Input Selections
LCD Display
Open: Parameters cannot be edited (except for U1-01 if the reference source is
Program Lockout
assigned to the digital operator).
Closed: Parameters can be edited and saved.
Closed: Samples the analog frequency reference and operates the drive at that
speed.
Ext Pump Fault
20: NO/Always Det,
Ramp to Stop
21: NC/Always Det,
Ramp to Stop
22: NO/During RUN,
Ramp to Stop
23: N.C., During run,
ramp to stop
20: N.O., Always detected, ramp to stop
24: NO/ Always Det,
21: N.C., Always detected, ramp to stop
Coast to Stop
22: N.O., During run, ramp to stop
25: NC/Always Det,
23: N.C., During run, ramp to stop
Coast to Stop
24: N.O., Always detected, coast to stop
26: NO/During RUN,
25: N.C., Always detected, coast to stop
Coast to Stop
26: N.O., During run, coast to stop
27: NC/During RUN,
27: N.C., During run, coast to stop
Coast to Stop
28: N.O., Always detected, Fast Stop
28: NO/Always Det,
29: N.C., Always detected, Fast Stop
Fast-Stop
2A: N.O., During run, Fast Stop
29: NC/Always Det,
2B: N.C., During run, Fast Stop
Fast-Stop
2C: N.O., Always detected, alarm only (continue running)
2A: NO/During RUN,
2D: N.C., Always detected, alarm only (continue running)
Fast-Stop
2E: N.O., During run, alarm only (continue running)
2B: NC/During RUN,
2F: N.C., During run, alarm only (continue running)
Fast- Stop
2C: NO/Always Det,
Alarm Only
2D: NC/Always Det,
Alarm Only
2E: NO/ During RUN,
Alarm Only
2F: NC/During RUN,
Alarm Only
PID Intgrl Reset
Closed: Resets the PID control integral value.
Open: Performs integral operation.
PID Intgrl Hold
Closed: Maintains the current PID control integral value.
Used in combination with input terminals set to Multi-Step Speed Reference 1, 2,
Multi-Step Ref 4
and 3. Use parameters d1-09 to d1-16 to set reference values.
Open: PID soft starter is enabled.
PID SFS Cancel
Closed: Disables the PID soft starter b5-17.
Closed: Inverts the PID input signal.
Open: Stop
Closed: Forward run
FwdRun 2Wire Seq
Note:
Open: Stop
Closed: Reverse run
RevRun 2WireSeq
Note:
Open: Stop
Closed: Run
Run/Stp 2WireSeq
Note:
Open: Forward
Closed: Reverse
FWD/REV 2WireSeq
Note:
CanOpenNID Setup
Closed: Node setup for SI-S3 enabled.
Closed: Drive ignores sequence timers and runs normally (based on b1-02/b1-16
source).
Description
Cannot be set together with settings 42 or 43.
Cannot be set together with settings 42 or 43.
Cannot be set together with settings 40 or 41.
Determines motor direction, but does not issue a Run command.
Cannot be set together with settings 40 or 41.
YASKAWA TOEP YAIP1W 01A YASKAWA AC Drive - iQpump1000 Quick Start Guide