4.6 Basic iQpump Setup and Application Preset Parameters
n
P1-06: Minimum Pump Speed
Sets the minimum speed at which the drive will run the pump. Most pumps cannot run at low speeds due to cavitation, so be
sure to consult the pump specification sheet for the minimum safe run speed.
No.
P1-06
n
P1-08: Low Feedback Level
Sets the level at which a Low Feedback alarm or fault will occur. When the PID feedback falls below the P1-08 setting for
the time set in P1-09, the drive will respond based on the setting in P1-10.
No.
P1-08
n
P1-09: Low Feedback Level Fault Delay Time
Sets the delay time after which a Low Feedback alarm or fault will occur. When the PID feedback falls below the P1-08 setting
for the time set in P1-09, the drive will respond based on the setting in P1-10.
No.
P1-09
n
P1-10: Low Feedback Selection
Selects the drive response to a Low Feedback condition. When the PID feedback falls below the P1-08 setting for the time set
in P1-09, the drive will respond based on the setting in P1-10.
No.
P1-10
Setting 0: Fault
Setting 1: Alarm
Setting 2: Digital out only
n
P1-11: High Feedback Level
Sets the level at which a High Feedback alarm or fault will occur. When the PID feedback rises above the P1-11 setting for
the time set in P1-12, the drive will respond based on the setting in P1-13.
No.
P1-11
n
P1-12: High Feedback Level Fault Delay Time
Sets the delay time after which a Low Feedback alarm or fault will occur. When the PID feedback rises above the P1-11 setting
for the time set in P1-12, the drive will respond based on the setting in P1-13.
No.
P1-12
n
P1-13: High Feedback Selection
Selects the drive response to a High Feedback condition. When the PID feedback rises above the P1-11 setting for the time
set in P1-12, the drive will respond based on the setting in P1-13.
No.
P1-13
166
Parameter Name
Minimum Pump Speed
Parameter Name
Low Feedback Level
Parameter Name
Low Feedback Level Fault Delay Time
Parameter Name
Low Feedback Selection
Parameter Name
High Feedback Level
Parameter Name
High Feedback Level Fault Delay Time
Parameter Name
High Feedback Selection
Setting Range
Setting Range
Setting Range
Setting Range
Setting Range
Setting Range
Setting Range
YASKAWA TOEP YAIP1W 01A YASKAWA AC Drive - iQpump1000 Quick Start Guide
0.0 to E1-04
0.0 to 6000.0
0 to 3600
0 to 2
0.0 to 6000.0
155.0 PSI
0 to 3600
0 to 2
Default
40.0 Hz
Default
0.0 PSI
Default
10 s
Default
0
Default
Default
5 s
Default
0