B.11 P: Pump Parameters
No.
(Addr.
Name
Hex)
P9-27
Network Recovery
(0E0E)
P9-28
NETSCAN Alarm Time NETSCAN AlrmTime
(0E0F)
P9-29
(0E10)
Net Start Delay
P9-30
Lag Drive Speed
(0E11)
Follower Gain
P9-31
Lag Drive Speed
(0E12)
Follower Bias
P9-32
Lag Follower
(0E13)
Deceleration Time
P9-33
Lag Follower
(0E14)
Deceleration Time
Active Time
P9-34
Low Feedback Quick
(0E15)
De-Stage
P9-40
(0E1B) Flow Rate Source
P9-41
Add Flow Level
(0E1C)
P9-42
Remove Flow Level
(0E1D)
P9-50
Water Level/Suction
(0E25)
Pressure Source
314
LCD Display
Determines the drive response when no messages are received
from the master for the time set in P9-26.
Network Recovery
0: Automatic. The drive will attempt to assume master
0: Automatic
functionality.
1: Slave/Resume
1: Slave/Resume. The drive will continue running when the
2: Slave/Stop
master is lost and will wait for a master to come online.
3: Fault MSL
2: Slave/Stop. The drive will stop running when the master is
lost and will wait for a master to come online.
3: Fault MSL. Fault the drive with an MSL (Master Lost).
Sets the amount of time that the slave drives will wait for a
message from the master before displaying a NETSCAN alarm.
Sets the amount of time that the network will wait before
selecting and starting the lead drive after the first drive on the
Net Start Delay
network has been put on AUTO Mode.
Sets the gain to be applied to the speed of the current lead drive
when P9-05 is set to 3. The bias to be applied is set in P9-31.
Lag Followr Gain
Sets the bias to be applied to the speed of the current lead drive
when P9-05 is set to 3. The gain to be applied is set in P9-30.
Lag Followr Bias
Sets the deceleration time when the P9-33 timer is running and
the drive is running as Lag Drive Speed Follower (P9-05 is set
Lag Followr Dcel
to 3).
Sets the time during which the deceleration time set in P9-32 is
effective. The drive will use the standard deceleration rate when
Lag Followr Dtim
it expires.
Setting this parameter to 0.0 disables the function.
Sets the low feedback level that will trigger a quick de-stage.
The quick de-stage ignores parameters P9-12 and P9-15 and
Low FB De-stage
only uses an internal 2 second delay.
Setting this parameter to 0.0 disables the function.
Defines the flow meter input source when P1-01, Pump Mode,
Flow Rate Source
is set to 3 (MEMOBUS network).
0: Analog Only
0: Analog
3: Network Only
3: Network
When P9-08 is set to 3 and the flow rate rises above this level
multiplied by the number of pumps running for the time set in
Add Flow Lvl
P9-11, the lead drive will request for a new lead drive through
the iQpump MEMOBUS network.
When P9-12 is set to 3 and the flow rate falls below this level
multiplied by the number of pumps running - 1 for the time set
Remove Flow Lvl
in P9-15, the lead drive will request to be removed from the
system through the iQpump MEMOBUS network.
Sets the signal to use for Water Level Control (Q4-oo) or
WL/SP Source
Suction Pressure Control (Q5-oo) when P1-01, Pump Mode,
0: Analog only
is set to 3 (MEMOBUS network).
1: Ana->Net, No Alrm
0: Analog only
2: Ana->Net, Alarm
1: Ana->Net, No Alrm
3: Network only
2: Ana->Net, Alarm
3: Network only
Description
YASKAWA TOEP YAIP1W 01A YASKAWA AC Drive - iQpump1000 Quick Start Guide
Values
Page
Default: 0
Range: 0 to 3
Default: 2.0 s
Min.: 1.0
Max.: 10.0
Default: 2.0 s
Min.: 0.0
Max.: 60.0
Default: 100.0%
Min.: 0.0
Max.: 300.0
Default: 0.00 Hz
Min.: -60.0
Max.: 60.0
Default: 60.0 s
Min.: 0.0
Max.: 1000.0
Default: 0.0 s
Min.: 0.0
Max.: 360.0
Default: 0.0 PSI
<1>
Min.: 0.0
Max.: 6000.0
Default: 0
Range: 0, 3
Default: 0.0
GPM
Min.: 0.0
Max.: 6000.0
Default: 0.0
GPM
Min.: 0.0
Max.: 6000.0
Default: 0
Range: 0 to 3