YASKAWA iQpump1000 Quick Start Manual page 158

Ac drive
Hide thumbs Also See for iQpump1000:
Table of Contents

Advertisement

4.6 Basic iQpump Setup and Application Preset Parameters
No.
E2-01
Note:
1. The number of decimal places in the parameter value depends on the drive model. This value has two decimal places (0.01 A) if the
drive is set for a maximum applicable motor capacity up to and including 11 kW, and one decimal place (0.1 A) if the maximum applicable
motor capacity is higher than 11 kW.
2. An oPE02 error will occur if the motor rated current in E2-01 is set lower than the motor no-load current in E2-03. Set E2-03 correctly
to prevent this error.
n
E2-04: Number of Motor Poles
Set the number of motor poles to E2-04. If Auto-Tuning completes successfully, the value entered to T1-06 will automatically
be saved to E2-04.
No.
E2-04
n
H1-01 to H1-08: Functions for Terminals S1 to S8
These parameters assign functions to the multi-function digital inputs. The various functions and settings are listed in
4.20.
No.
H1-01
Multi-Function Digital Input Terminal S1 Function Selection
H1-02
Multi-Function Digital Input Terminal S2 Function Selection
H1-03
Multi-Function Digital Input Terminal S3 Function Selection
H1-04
Multi-Function Digital Input Terminal S4 Function Selection
H1-05
Multi-Function Digital Input Terminal S5 Function Selection
H1-06
Multi-Function Digital Input Terminal S6 Function Selection
H1-07
Multi-Function Digital Input Terminal S7 Function Selection
H1-08
Multi-Function Digital Input Terminal S8 Function Selection
<1> Number appearing in parenthesis is the default value after performing a 3-Wire initialization (A1-03 = 3330).
Setting
0
3-Wire sequence
3
Multi-Step Speed Reference 1
4
Multi-Step Speed Reference 2
5
Multi-Step Speed Reference 3
6
Jog reference selection
7
Accel/decel time selection 1
8
Baseblock command (N.O.)
9
Baseblock command (N.C.)
A
Accel/decel ramp hold
B
Drive overheat alarm (oH2)
C
Analog terminal input selection
F
Through mode
10
Up command
11
Down command
12
Forward Jog
13
Reverse Jog
14
Fault reset
15
Fast Stop (N.O.)
17
Fast Stop (N.C.)
18
Timer function input
19
PID disable
158
Parameter Name
Motor Rated Current
Refer to Power Ratings on page 234
Parameter Name
Number of Motor Poles
Parameter Name
Table 4.20 Multi-Function Digital Input Terminal Settings
Function
for details.
Setting
Range
1 to 9F
40 (F)
1 to 9F
F: Through Mode
0 to 9F
26: External Pump Fault
0 to 9F
14: Fault Reset
0 to 9F
8D (0)
0 to 9F
80 (3)
0 to 9F
81 (4)
0 to 9F
F (6)
Page
Setting
1A
Accel/decel time selection 2
1B
Program lockout
1E
Reference sample hold
20 to 2F Ext. pump fault
30
PID integral reset
31
PID integral hold
Multi-Step Speed
32
Reference 4
34
PID soft starter cancel
35
PID input level selection
Forward run command
40
(2-Wire sequence)
Reverse run command
41
(2-Wire sequence)
Run command
42
(2-Wire sequence 2)
FWD/REV command
43
(2-Wire sequence 2)
47
Node setup
51
Sequence Timer Disable
52
Sequence Timer Cancel
60
DC Injection Braking command
YASKAWA TOEP YAIP1W 01A YASKAWA AC Drive - iQpump1000 Quick Start Guide
Setting Range
10% to 200% of the drive
rated current
Setting Range
2 to 48
Default
<1>
: Forward Run Command (2-Wire sequence)
<1>
: Multi Setpoint 1
<1>
: HAND Mode
<1>
: HAND Mode 2
<1>
: Through Mode
Function
Default
Determined by
o2-04
Default
2
Table
Page