YASKAWA iQpump1000 Quick Start Manual page 283

Ac drive
Hide thumbs Also See for iQpump1000:
Table of Contents

Advertisement

H2-oo
Function
Setting
84
Pump 6 Control
89
Output 1 Limit
8B
Lube Pump
8F
Internal Fan On
91
Pump Fault
92
Transducer Loss
93
Setptoint Not Met
94
Loss of Prime
95
Volute Thermostat Fault Volute-TStat Flt
96
High Feedback
97
Low Feedback
98
Low Flow
99
Accum Level
9A
High Flow
9B
Low Water Level
9C
Low Suction
9D
High Suction
A2
Sleep Active
A3
Start Delay
A4
Pre-Charge
A5
Anti-Jam Active
A9
Thrust Mode
AA
Utility Start Delay
100 to
Function 0 to AA with
1AA
inverse output
YASKAWA TOEP YAIP1W 01A YASKAWA AC Drive - iQpump1000 Quick Start Guide
H2 Multi-Function Digital Output Settings
LCD Display
Contactor control for a sixth pump.
Pump 6 Control
The function is active in contactor multiplex mode only (P1-01 = 1) and when
P3-01 is set to a value greater than 4.
Closed: Drive output speed is being limited due to the output current limit or the
Output I Lim
single phase foldback regulator.
Lube Pump
Closed: Energizes for the time set in P4-31 each time the drive is supposed to start.
Internal Fan On
Internal Fan On
Closed when any of the following faults are active:
• Low feedback
• High feedback
• Low water
Pump Fault
• High water
• NMS-Setpoint not met
• POC-Pump over cycle
• THMS-Thermostat input
• External pump fault
Closed: The analog output associated with PID feedback has risen above 21 mA
Transducer Loss
or fallen below 3 mA or a Transducer Loss alarm or fault is active.
SetPoint Not Met
Closed: During an "NMS-Setpoint Not Met" condition.
Loss of Prime
Closed: During an "LOP-Loss of Prime" condition.
Closed: Volute-Thermostat digital input is active.
Closed: During a "High Feedback" condition as defined by P1-11 and P1-12 OR
High Feedback
Closed: During a "High FB/Water" fault OR
Closed: During a "High Feedback" alarm
Closed: During a "Low Feedback" condition as defined by P1-08 and P1-12 OR
Low Feedback
Closed: During a "Low FB/Water" fault OR
Closed: During a "Low Feedback" alarm
Closed: During the "Low Flow Fault" condition OR
Low Flow
Closed: During a Low Flow condition set by P6-06 to P6-08, including a "Low
Flow" alarm
Closed: Accumulated level has exceeded the P6-11 to P6-14 settings OR
Accum Level
Closed: During the "Accum Level" fault
Closed: During the "High Flow Fault" condition OR
High Flow
Closed: During a "High Flow" condition set by P6-17 and P6-18, including a "High
Flow" alarm
Closed: The water level has dropped below the Low Detection Level set in Q4-09
Low Water Level
for longer than the Low Level Detection Delay Time set in Q4-09 or if there is a
LOWWL – Low Water Level Fault.
Closed: The suction pressure has dropped below the Low Suction Pressure
Low Suction
Detection Level set in Q5-09 for longer than the Low Suction Pressure Delay Time
set in Q5-10 or if there is a LOSUC – Low Suction Pressure Fault.
Closed: The suction pressure has risen above the High Suction Pressure Detection
High Suction
Level set in Q5-12 for longer than the High Suction Pressure Delay Time set in
Q5-13 or if there is a HISUC – High Suction Pressure Fault.
Closed: The drive is not running due to the Sleep function (does not include Sleep
Sleep Active
Boost).
Closed: Feedback has risen above the start level (or fallen below for Inverse PID)
Start Delay
and the start timer is timing.
Pre-Chg Active
Closed: Drive is in Pre-Charge mode.
Anti-Jam Active
Closed: The anti-jam function is active (configured by P7-oo).
Closed: The Thrust Bearing feature is active (output frequency is between 0 and
Thrust Mode
the value of P4-12).
Closed: The drive is stopped and waiting for the utility delay timer set in P4-17 to
Utility Delay
expire.
Inverts the output switching of the multi-function output functions.
Set the last two digits of 1oo to reverse the output signal of that specific function.
B.7 H Parameters: Multi-Function Terminals