4.6 Basic iQpump Setup and Application Preset Parameters
The wait time t is determined by the output frequency when the Run command is removed and by the active deceleration time.
n
b3-01: Speed Search Selection at Start
Determines if Speed Search is automatically performed when a Run command is issued.
No.
b3-01
Setting 0: Disabled
This setting starts operating the drive at the minimum output frequency when the Run command is entered. If external Speed
Search 1 or 2 is already enabled by a digital input, the drive will start operating with Speed Search.
Setting 1: Enabled
This setting performs Speed Search when the Run command is entered. The drive begins running the motor after Speed Search
is complete.
n
b5-01: PID Function Setting
Enables and disables the PID operation and selects the PID operation mode.
No.
b5-01
Setting 0: PID disabled
Setting 1: Output frequency = PID output 1
The PID controller is enabled and the PID output builds the frequency reference. The PID input is D controlled.
n
b5-03: Integral Time Setting (I)
Sets the time constant used to calculate the integral of the PID input. The shorter the integral time set to b5-03, the faster the
offset will be eliminated. If the integral time is set too short, however, overshoot or oscillation may occur. To turn off the
integral time, set b5-03 to 0.00.
No.
b5-03
n
b5-09: PID Output Level Selection
Reverses the sign of the PID controller output signal. Normally a positive PID input (feedback smaller than setpoint) leads to
positive PID output.
No.
b5-09
Setting 0: Normal Output
A positive PID input causes an increase in the PID output (direct acting).
Setting 1: Reverse Output
A positive PID input causes a decrease in the PID output (reverse acting).
156
Run wait time t
Active deceleration time
Min Baseblock Time (L2-03)
Min output
frequency
Figure 4.32 Run Wait Time Depending on Output Frequency
Parameter Name
Speed Search Selection at Start
Parameter Name
PID Function Setting
Name
Integral Time Setting (I)
Parameter Name
PID Output Level Selection
Output frequency
when Stop command
was entered
Setting Range
Setting Range
Setting Range
Setting Range
YASKAWA TOEP YAIP1W 01A YASKAWA AC Drive - iQpump1000 Quick Start Guide