B.11 P: Pump Parameters

u

P1: Pump Basic

No.
(Addr.
Name
Hex)
P1-01
Pump Mode
(0C00)
P1-02
System Units
(0C01)
P1-03
Feedback Device
(0C02)
Scaling
P1-04
(0C03) Start / Draw Down
Level
P1-05
(0C02) Start Level Delay Time S-Lev Delay Time
P1-06
(0C05) Minimum Pump Speed Min. Pump Speed
P1-07
Minimum Pump Speed
(0C06)
Units
<3>
P1-08
(0C07) Low Feedback Level
P1-09
(0C08) Low Feedback Level
Fault Delay Time
YASKAWA TOEP YAIP1W 01A YASKAWA AC Drive - iQpump1000 Quick Start Guide
LCD Display
Pump Mode
0: Drive only
0: Drive Only
1: Contactor lag
1: Contactor Lag
3: MEMOBUS network
3: Memobus Network
System Units
0: No unit
0: No Unit
1: PSI: Pounds per square inch
1: PSI :lb/SqrInch
2: Pa: Pascals
2: Pa:Pascals
3: Bar: Bar
3: Bar:Bar
4: "WC: Inch of water
4: "WC:InchOfWater
5: "Hg: Inch of Mercury
5: "Hg:Inch Mercury
6: ft: feet
6: ft: feet
7: m: meters
8: °F: Degrees Fahrenheit
7: m: meters
8: °F:DegFarenheit
9: °C: Degrees Celsius
9: °C:DegCelsius
10: Percent
10: %: Percent
25: Flow (Use P6-04)
25: Flow (use P6-04)
Sets the scaling of feedback device in user-set units.
FB Dev. Scaling
The system starts when the feedback level drops below the start
level for the time set in P1-05. This level also specifies the wake-
up level when the drive is in Sleep Mode.
When this parameter is set to a negative value, the feedback level
must drop that amount below the setpoint.
Setting this parameter to 0.0 disables the function. When P1-01,
Start-DrawDn Lvl
Pump Mode, is set to 3 (MEMOBUS network), this function is
active only on the first drive in the network.
Note:
The system starts when the feedback level drops below the start
level for the time set in this parameter.
Minimum frequency at which the drive will run. Applies to both
HAND and Automatic modes.
Note:
Sets the units and decimal place for parameter P1-06.
0: Hz
MinPumpSpdUnits
1: RPM
0: Hz
1: RPM
Note:
Sets the lower detection level for the PID feedback.
Low FB Level
Sets the amount of delay time from when the low feedback is
detected until the drive faults on an "LFB Low Feedback" fault.
Note:
Low Lvl FLT Time
Description
<1>
When PID operates in reverse mode, the system
will start when the feedback has risen above the
start level for the time set to P1-05.
For minimum pump frequency, the drive will use
the highest setting from among P1-06, P4-12
(Thrust Bearing Frequency), or d2-02 (Reference
Lower Limit).
Changing this parameter will reset the P1-06
default value.
1. This parameter is effective only when P1-10
is set to 0 (Fault).
2. When P1-01 is set to 3, parameter P9-18 uses
this value to calculate the quick de-stage
feedback level.
B.11 P: Pump Parameters
Values
Page
Default: 0
164
Range: 0, 1, 3
Default: 1
Range: 0 to 10;
165
25
Default: 145.0
<2>
PSI
165
Min.: 0.1
Max.: 6000.0
Default: 0.0
Min.: -999.9
165
Max.: 999.9
Default: 1 s
Min.: 0
165
Max.: 3600
Default: 40.0 Hz
<3>
166
Min.: 0.0
Max.: [E1-04]
Default: 0
Range: 0, 1
Default: 0.0 PSI
<2>
166
Min.: 0.0
Max.: 6000.0
Default: 10 s
Min.: 0
166
Max.: 3600
B
301