P2-01: Sleep Level Type
Selects which data source the drive will use to determine if it should activate the sleep function. This parameter is application-
dependent and should be set in conjunction with the type of system data is available. Choose the data type that best represents
a low-activity condition for the system.
Note:
Set this parameter prior to changing other parameters related to the Sleep Function, as internal scaling is based on P2-01.
No.
P2-01
Setting 0: Output frequency
Setting 1: Output current
Setting 2: Feedback
Setting 3: Output speed (RPM)
Setting 4: Flow meter (requires flow meter)
n
P2-02: Sleep Level
Sets the level at which the drive will enter sleep mode. The drive will enter sleep mode when the monitored data falls below
the P2-02 setting for the time set in P2-03.
No.
P2-02
n
P2-03: Sleep Delay Time
Sets the delay time after which the drive will enter sleep mode. The drive will enter sleep mode when the monitored data falls
below the P2-02 setting for the time set in P2-03.
No.
P2-03
n
P3-00: Number of Lag Pumps
Sets the number of lag pumps in the system. When using Contactor Multiplexing for the control lag pumps, first set P1-01 to
1. Then select the number of lag pumps to be controlled in P3-00. Set the corresponding multi-function digital outputs for lag
pumps (H2-oo = 80-82 and F5-oo = 83-84). The methods used to determine lag pump staging and de-staging order are
selected in P1-30 and P1-31.
No.
P3-00
n
P3-50: Pump 2 Frequency Shutdown Level
Sets the level at which the first lag pump (2nd pump in the system) will shut down or de-stage. This parameter is effective
when the P3-01 is set to 0 or 2 (pump staging is based on output frequency). When the output frequency falls below the P3-50
leel for the time set in P3-09, the pump will be de-staged.
No.
P3-50
n
P3-60: Pump 3 Frequency Shutdown Level
Sets the level at which the second lag pump (3rd pump in the system) will shut down or de-stage. This parameter is effective
when the P3-01 is set to 0 or 2 (pump staging is based on output frequency). When the output frequency falls below the P3-50
leel for the time set in P3-09, the pump will be de-staged.
No.
P3-60
YASKAWA TOEP YAIP1W 01A YASKAWA AC Drive - iQpump1000 Quick Start Guide
4.6 Basic iQpump Setup and Application Preset Parameters
Parameter Name
Sleep Level Type
Parameter Name
Sleep Level
Parameter Name
Sleep Delay Time
Parameter Name
Number of Lag Pumps
Parameter Name
Pump 2 Frequency Shutdown Level
Parameter Name
Pump 3 Frequency Shutdown Level
Setting Range
0 to 4
Setting Range
0.0 to 6000.0
Setting Range
0 to 3600
Setting Range
1 to 5
Setting Range
0.0 to 400.0
Setting Range
0.0 to 400.0
Default
0
Default
0.0 Hz
Default
0 s
Default
1
4
Default
40.0 Hz
Default
40.0 Hz
167