P6: Flow Meter Setup

No.
(Addr.
Name
Hex)
P6-01
Flow Meter Scaling
(0D5E)
P6-02
(0D5F) Turbine Input Scaling
(Course)
P6-03
(0D60) Turbine Input Scaling
(Fine)
YASKAWA TOEP YAIP1W 01A YASKAWA AC Drive - iQpump1000 Quick Start Guide
LCD Display
Selects whether the drive will permit switching between HAND
HAND/AUTO @ Run
and AUTO Modes while running.
0: Disabled
0: Disabled
1: Enabled
1: Enabled
Oper HAND Key
Enables and disables the HAND key on the HOA keypad.
0: Disabled
0: Disabled
1: Enabled
1: Enabled
Sets the frequency reference used when HAND Mode 2 is
active.
HAND Reference 2
Detects loss of prime in the pump.
When the measured quantity determined by P1-18 drops below
this level for the time set in P1-20 and the output frequency is
HandRef1 LOP Lvl
at the level set in P5-02, a "Loss of Prime" condition occurs.
The drive responds to the "Loss of Prime" condition depending
on the setting of P1-22, Loss of Prime Selection.
Detects loss of prime in the pump.
When the measured quantity determined by P1-18 drops below
this level for the time set in P1-20 and the output frequency is
HandRef2 LOP Lvl
at the level set in P5-05, a "Loss of Prime" condition occurs.
The drive responds to the "Loss of Prime" condition depending
on the setting of P1-22, Loss of Prime Selection.
Selects whether parameters P5-02 and P5-05 are changed via
HAND MOP Sel
MOP from the home screen.
0: Disabled
0: Disabled
1: Enabled
1: Enabled
LCD Display
When an analog input is used for the flow rate, this parameter
performs the following functions:
• Enables and disables flow meter functions. This parameter
must be set to a value greater than 0 to enable flow meter
functions.
• Sets the scaling for the "Flow Rate" analog input.
• Sets the scaling for the "Flow Rate" analog output.
• Sets the display scaling when "Flow Rate" is used as the PID
Flow Meter Scale
feedback.
When an pulse input is used for the flow rate, this parameter
performs the following functions:
• Enables and disables flow meter functions. Parameter must
be set to a value greater than zero to enable flow meter
functions.
• Sets the scaling for the "Flow Rate" analog output.
• Sets the display scaling when "Flow Rate" is used as the PID
feedback.
Sets the scaling for the turbine in pulses per gallon.
Pulses/Gallon = P6-02 + P6-03
Turbine Scale 1
This parameter is internally lower-limited to 0.0001 ppG.
Turbine Scale 2
B.11 P: Pump Parameters
Description
Description
Values
Page
Default: 0
Range: 0, 1
Default: 1
169
Range: 0, 1
Default: 0.0 Hz
Min.: 0
Max.: [E1-04]
Default: 0.0 PSI
<1>
Min.: 0.0
Max.: 1000.0
Default: 0.0 PSI
<1>
Min.: 0.0
Max.: 1000.0
Default: 0
Range: 0, 1
Values
Page
Default: 0.0
GPM
Min.: 0.0
Max.: 6000.0
Default: 1 ppG
Min.: 0
Max.: 6000
Default: 0.0000
ppG
Min.: 0.0000
Max.: 0.9999
B